Thứ Năm, 29 tháng 7, 2021

American Water Heater NRXSS00109, homeappliance





Download!

Installation and Operating Manual HYBRID GAS WATER HEATERS POWER VENT GAS MODELS www.americanwaterheater.com ANSI Z21.10.3b-2008 • For Your Safety • AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER. ALL TECHNICAL AND WARRANTY QUESTIONS: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED. KEEP THIS MANUAL IN THE POCKET ON HEATER FOR FUTURE REFERENCE WHENEVER MAINTENANCE ADJUSTMENT OR SERVICE IS REQUIRED. 0710 316888-004 Rev. 00 TABLE OF CONTENTS SAFE INSTALLATION, USE AND SERVICE 3 GENERAL SAFETY 4 INTRODUCTION 6 Get To Know Your Water Heater - Gas Models. . . . . 8 Replacement Parts And Deliming Products . . . . . . . 8 INSTALLATION CONSIDERATIONS 9 Rough In Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 9 Water Piping - Mixing Valve Usage . . . . . . . . . . . . . .11 Facts To Consider About Location. . . . . . . . . . . . . . 12 Handle Installation. . . . . . . . . . . . . . . . . . . . . . . . . . 13 Earthquake Zones. . . . . . . . . . . . . . . . . . . . . . . . . . 14 Combustion Air And Ventilation . . . . . . . . . . . . . . . . 16 Appliances In Unconfi ned Spaces . . . . . . . . . . . . . 16 Appliances In Confi ned Spaces . . . . . . . . . . . . . . . 16 Chemical Vapor Corrosion . . . . . . . . . . . . . . . . . . . 18 Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Closed Water Systems . . . . . . . . . . . . . . . . . . . . . . 18 Thermal Expansion . . . . . . . . . . . . . . . . . . . . . . . . . 18 Hard Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Temperature-pressure Relief Valve. . . . . . . . . . . . . 19 Gas Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Sediment Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Gas Line Purging . . . . . . . . . . . . . . . . . . . . . . . . . . 22 High Altitude Installations . . . . . . . . . . . . . . . . . . . . 22 Flooding/freezing. . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Filling The Water Heater . . . . . . . . . . . . . . . . . . . . . 22 Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Vent Pipe Termination . . . . . . . . . . . . . . . . . . . . . . . 23 Planning The Vent System . . . . . . . . . . . . . . . . . . . 23 Condensate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Installation Of Vent System . . . . . . . . . . . . . . . . . . . 25 Vent Terminal Installation, Sidewall. . . . . . . . . . . . . 25 Sequence Of Installations . . . . . . . . . . . . . . . . . . . . 26 Installation Sequence . . . . . . . . . . . . . . . . . . . . . . . 26 Installation Of Vent System, Sidewall . . . . . . . . . . . 27 Installation Of Vertical Vent System . . . . . . . . . . . . 27 Vent Pipe Preparation . . . . . . . . . . . . . . . . . . . . . . . 28 Connection To Vent Pipe. . . . . . . . . . . . . . . . . . . . . 30 U.S. Power Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Electrical Connections. . . . . . . . . . . . . . . . . . . . . . . 32 CALIBRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 OPERATING INSTRUCTIONS 33 Display Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Lighting Instructions . . . . . . . . . . . . . . . . . . . . . . . . 36 Heat Cycle Defi nitions. . . . . . . . . . . . . . . . . . . . . . . 37 Temperature Regulation . . . . . . . . . . . . . . . . . . . . . 38 Unique Hybrid Features . . . . . . . . . . . . . . . . . . . . . 39 Temperature Regulation . . . . . . . . . . . . . . . . . . . . . 41 Constant Output Temperature Control . . . . . . . . . . 42 Start Up Conditions . . . . . . . . . . . . . . . . . . . . . . . . . 42 Operational Conditions . . . . . . . . . . . . . . . . . . . . . . 42 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Housekeeping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Venting System Inspection . . . . . . . . . . . . . . . . . . . 43 Burner Operation And Inspection . . . . . . . . . . . . . . 43 Anode Rod Inspection. . . . . . . . . . . . . . . . . . . . . . . 43 Anode Rod Replacement . . . . . . . . . . . . . . . . . . . . 44 Temperature-pressure Relief Valve Operation . . . . 44 Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Snow Accumulation. . . . . . . . . . . . . . . . . . . . . . . . . 44 Cleaning The Inlet Water Filter . . . . . . . . . . . . . . . . 44 Cleaning The Heat Engine . . . . . . . . . . . . . . . . . . . 45 Flushing The Heat Exchanger (Lime Build-up) . . . . 45 Draining The Tank . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Fault Indication And Error Codes . . . . . . . . . . . . . . 46 Diagnostic Display. . . . . . . . . . . . . . . . . . . . . . . . . . 47 TROUBLESHOOTING 51 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Leakage Checkpoints . . . . . . . . . . . . . . . . . . . . . . . 53 Parts Identifi cation. . . . . . . . . . . . . . . . . . . . . . . . . . 54 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . 56 NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Fill out and keep with water heater. IMPORTANT INFORMATION Model Number _________________________________________ Serial Number __________________________________________ Installation Information: Date Installed __________________________________________ Company's Name _______________________________________ Street or P.O. Box _______________________________________ City, State, and Zip Code _________________________________ Phone Number ____________ Plumber's Name _______________ 2 www.americanwaterheater.com SAFE INSTALLATION, USE AND SERVICE Your safety and the safety of others is extremely important in the installation, use and servicing of this water heater. Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important that the meaning of each safety message is understood by you and others who install, use or service this water heater. All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message and how to avoid the risk of injury. The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of substances known to the State of California to cause cancer, birth defects, or other reproductive harm, and requires businesses to warn of potential exposure to such substances. This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm. This appliance can cause low level exposure to some of the substances listed. IMPORTANT DEFINITIONS • Qualifi ed Installer or Service Agency: Installation and service of this water heater requires ability equivalent to that of a Qualifi ed Agency (as defi ned by ANSI below) in the fi eld involved. Installation skills such as plumbing, air supply, venting, gas supply, electrical supply are required in addition to electrical testing skills when performing service. • ANSI Z223.1 2006 Sec. 3.3.83: "Qualifi ed Agency" - "Any individual, fi rm, corporation or company that either in person or through a representative is engaged in and is responsible for (a) the installation, testing or replacement of gas piping or (b) the connection, installation, testing, repair or servicing of appliances and equipment; that is experienced in such work; that is familiar with all precautions required; and that has complied with all the requirements of the authority having jurisdiction.". • Gas Supplier: The Natural Gas or Propane Utility or service who supplies gas for utilization by the gas burning appliances within this application. The gas supplier typically has responsibility for the inspection and code approval of gas piping up to and including the Natural Gas meter or Propane storage tank of a building. www.americanwaterheater.com 3 GENERAL SAFETY 4 www.americanwaterheater.com GENERAL SAFETY WARNING Breathing Hazard - Carbon Monoxide Gas • Install vent system In accordance with codes. • Do not operate water heater if flood damaged. • Special Consideration must be taken with installations above 11,000' (3,352m) for standard models. • Do not operate if soot buildup is present. • Do not obstruct water heater air intake with insulating jacket. • Do not place chemical vapor emitting products DANGER FLAMMBLE Flammable Vapors near water heater. • Gas and carbon monoxide detectors are available. • No vent damper installation is compatible with this power vented water heater. • DO not elevate the condensate hose on the bottom of the water heater above the bracket attached to the side of the unit. This must be true for the entire length of the hose including the exit into an appropriate drain. • Condensate lines must be free and clear of debris and must not allow back flow through the hose. The condensate lines must be able to flow freely to an appropriate drain. • Do not allow condensate lines to become crimped closed. • Analyze the entire vent system to make sure that condensate will not become trapped in a section of vent pipe and therefore reduce the open cross Vapors from flammable liquids may explode and catch fire causing death or severe burns. Do not use or store flammable products such as gasoline, solvents or adhe sives in the same room or area near the water heater. Keep flammable products: 1. far away from heater, 2. in approved containers, 3. tightly closed and 4. out of children's reach. Water heater has a main burner and spark generator. The spark generator: 1. can be triggered at any time and 2. the spark will ignite flammable vapors. Vapors: 1. cannot be seen, 2. are heavier than air, 3. go a long way on the floor and 4. can be carried from other rooms to the the electodes by air currents. sectional area of the vent. Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. Installation: Do not install the water heater where flammable products will be stored or used. www.americanwaterheater.com 5 INTRODUCTION Thank You for purchasing this water heater. Properly 5. installed and maintained, it should give you years of trouble free service. Abbreviations Found In This Instruction Manual: • CSA - Canadian Standards Association • ANSI - American National Standards Institute • NFPA - National Fire Protection Association • ASME - American Society of Mechanical Engineers 6. • GAMA - Gas Appliance Manufacturer's Association • UL - Underwriters Laboratories Inc. This gas-fi red water heater is design certifi ed by CSA International under American National Standard/CSA Standard for Gas Water Heaters ANSI Z21.10.3 • CSA 4.3 (current edition). 7. PREPARING FOR THE INSTALLATION Carefully plan the place where you are going to put the water heater. Correct combustion, vent action, and vent pipe installation are very important in preventing death from possible carbon monoxide poisoning and fi res (see Figures 1 and 3). Examine the location to ensure the water heater complies with the "Facts to Consider About Location" section in this manual. For California installation this water heater must be braced, anchored, or strapped to avoid falling or moving during an earthquake. See instructions for correct installation procedures. Instructions may be obtained from California Offi ce of the State Architect, 400 P Street, Sacramento, CA 95814. Massachusetts Code requires this water heater to be installed in accordance with Massachusetts 248-CMR 2.00: State Plumbing Code and 248-CMR 5.00, See Read the "General Safety" section, of this manual 1. first and then the entire manual carefully. If you 8. don't follow the safety rules, the water heater will not 9. operate properly. It could cause DEATH, SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE. This manual contains instructions for the installation, operation, and maintenance of the gas-fi red water heater. You must read and be aware of the warnings placed throughout the manual. All warnings and all instructions are essential to the proper operation of the water heater and your safety. Since we cannot put everything on the fi rst few pages, READ THE ENTIRE MANUAL BEFORE ATTEMPTING TO INSTALL OR OPERATE THE WATER HEATER. The installation must conform with these instructions 2. and the local code authority having jurisdiction. In the absence of local codes, the installation must comply with the current editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the National Electrical Code, NFPA 70. Documents are available from: page 8. Complies with SCAQMD rule #1146 and districts having equivalent NOx requirements. Complies with California's legislation AB1953 and Vermont's legislation Act 193 requirement of a weighted average maximum of 0.25% lead. Canadian Standards Association, 5060 Spectrum Way, Mississauga, Ontario, Canada L4W 5N6 NFPA documents are also available from: National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269. The water heater when installed must be grounded in 3. accordance with the local codes, or in the absence of local codes: the National Electrical Code (NFPA 70). 4. If after reading this manual you have any questions or do not understand any portion of the instructions, call the local gas utility or the manufacturer whose name appears on the rating plate. 6 www.americanwaterheater.com www.americanwaterheater.com 7 GET TO KNOW YOUR WATER HEATER - GAS MODELS A Mixing Valve*** B Hot Water Outlet (Tempered)*** C Pipe Insulation*** D Inlet Water Shutoff Valve*** E Cold Water Inlet*** F Expansion Tank*** G Vent Termination Elbow** H Access Door (Heat Engine) I Earthquake Strap*** J Power Cord* K Main Manual Gas Shutoff Valve*** L Gas Supply*** M Sediment Pocket*** N Condensate Tube O Drain Pan*** P Drain Valve Q Heat Engine Hose - Cold In R Casing Door (Plastic) S Display Enclosure (Plastic) T Heat Engine Hose - Hot Out U Side Casing (Plastic) V Top Casing Enclosure (Plastic) W Exhaust Elbow Assembly X T&P Relief Valve Y Anode Z Inlet Dip Tube * CAUTION HARNESS HAS 120 VAC. IN OPERATION. ** See "Planning the Vent System," "Installation of Vent System" and "Condensate" for more information. *** These items not included. REPLACEMENT PARTS AND DELIMING A V U T S B C D E F G H I J K L M PRODUCTS Replacement parts and recommended delimer may be ordered through authorized servicers or distributors. When ordering parts, provide complete model and serial numbers (see rating plate), quantity and name of part desired. Standard hardware items may be purchased locally. X N W Y Z R Q P O N FIGURE 1 8 www.americanwaterheater.com INSTALLATION CONSIDERATIONS ROUGH IN DIMENSIONS Top View Left Side View FIGURE 2 Capacity, Gas and Electrical Characteristics Model Approx. Capacity Input Gas Type Gas Supply Pressure Manifold Pressure Electrical Characteristics U.S. Gals. Litres BTU/hr Max. in. WC (kPa) Min. in. WC (kPa) in. WC (kPa) Volts/Hz Amperes GH-90N 25 94.6 100,000 Nat. 14.0 (3.49) 5.0 (1.25) 4.2 (1.05) 120/60 2.5 Minimum gas supply pressure must be maintained under both load and no load (dynamic and static) conditions. Manifold Pressure is preset on the gas valve by the manufacturer; DO NOT ATTEMPT TO ADJUST! Thermal effi ciency is 90%. If the hardness of your water supply is more than of 12 grains per gallon (200 mg/L), if your water supply is acidic or otherwise impure, the water supply must be treated with approved methods in order to ensure full warranty coverage. Problems resulting from the forma tion of scale are not covered by the warranty. Minimum Clearance To Combustibles Service Clearance Test Pressure P.S.I. Top Front Vent Back Sides Floor Front Sides 0 0 0 0 0 0 21" (53.3 cm) 12" (30.5 cm) 300 This appliance must be installed in accordance with local codes or, in the absence of local codes, the "National Fuel Gas Code" ANSI Z223.1/NFPA 54 or the "Natural Gas and Propane Installation Code" CAN/CSAB149.1. Not for installation in a Manufactured Home (Mobile Home). This water heater is suitable for water (potable) heating only. This water heater is suitable for installation in a closet or alcove. www.americanwaterheater.com 9 INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS For all side wall terminated, horizontally vented power vent, gas fueled water heaters installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfi tter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the fl oor level where the gas equipment is to be installed. In addition, the installing plumber or gasfi tter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the sidewall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualifi ed licensed professionals for the installation of hard wired carbon monoxide detectors. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent fl oor level. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed. APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and CSA certifi ed. SIGNAGE A metal or plastic identifi cation plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS." INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4. EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: 1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and 2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building, or structure used in whole or in part for residential purposes. MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include: 1. Detailed instructions for the installation of the venting system design or the venting system components; and 2. A complete parts list for the venting system design or venting system. MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the fl ue gases, but identifi es "special venting systems," the following requirements shall be satisfi ed by the manufacturer: 1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and 2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions. A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation. 10 www.americanwaterheater.com WATER PIPING - MIXING VALVE USAGE TEMPERED POTABLE WATER SUGGESTED PIPING ARRANGEMENT FOR TOP CONNECTIONS SHUT-OFF VALVE COLD WATER INLET THERMAL EXPANSION TANK MIXING VALVE (OPTIONAL) PIPE INSULATION (RECOMMENDED) METAL TEMPERED POTABLE WATER TEMPERATURE PRESSURE RELIEF VALVE DISCHARGE PIPE (DO NOT CAP OR PLUG) DRAIN PAN 6 in. (15cm) MAX. AIR GAP FLOOR DRAIN VALVE FIGURE 3 TO SUITABLE DRAIN DRAIN This appliance has been design certifi ed as complying with ANSI Z21.10.3/CSA 4.3 (latest revision) for water heaters and is considered suitable for: Water (Potable) Heating: All models are considered suitable for water (potable) heating. Please note the following: The system should be installed only with piping that is suitable for potable (drinkable) water such as copper, CPVC, PEX or polybutylene. DO NOT use PVC water piping. DO NOT use any pumps, valves, or fi ttings that are not compatible with potable water. DO NOT use valves that may cause excessive restriction to water fl ow. Use full fl ow ball or gate valves only. DO NOT use any lead based solder in potable water lines. Use appropriate tin-antimony or other equivalent material. DO NOT tamper with the gas control/thermostat, igniter, fl ammable vapor sensor or temperature and pressure relief valve. Tampering voids all warranties. Only qualifi ed service technicians should service these components. DO NOT use with piping that has been treated with chromates, boiler seal, or other chemicals. DO NOT add any chemicals to the system piping which will contaminate the potable water supply. HOTTER WATER CAN SCALD: Water heaters are intended to produce hot water. Water heated to a temperature which will satisfy space heating, clothes washing, dish washing, and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, and the physically or developmentally disabled. If anyone using hot water from this heater fi ts into one of these www.americanwaterheater.com 11 groups or if there is a local code or state law requiring a certain temperature water at the hot water tap, then you must take special precautions. In addition to using the lowest possible temperature setting that satisfi es your hot water needs, a means such as a Mixing Valve, should be used at the hot water taps used by these people or at the water heater (see Figure 3). Mixing valves are available at plumbing supply or hardware stores. Consult a Qualifi ed Installer or Service Agency. Follow the mixing valve manufacturer's instructions for installation of the valves. Before changing the factory setting on the thermostat, read the "Temperature Regulation" section in this manual. FACTS TO CONSIDER ABOUT LOCATION Carefully choose an indoor location for the new water heater, because the placement is a very important consideration for the safety of the occupants in the building and for the most economical use of the appliance. This water heater is not for use in manufactured (mobile) homes or outdoor installation. Whether replacing an old water heater or putting the water heater in a new location, the following critical points must be observed: such a manner that if the tank or any connections should leak, the fl ow will not cause damage to the structure. For this reason, it is not advisable to install the water heater in an attic or upper fl oor. When such locations cannot be avoided, a suitable metal drain pan should be installed under the water heater. Drain pans are available at your local hardware store. Such a drain pan must have a clearance of at least 1.0 in. (2.5cm) greater than any point on the water heater's outer jacket and must be piped to an adequate drain. The pan must not restrict combustion air fl ow. See Figure 1. Water heater life depends upon water quality, water pressure and the environment in which the water heater is installed. Water heaters are sometimes installed in locations where leakage may result in property damage, even with the use of a drain pan piped to a drain. However, unanticipated damage can be reduced or prevented by a leak detector or water shut-off device used in conjunction with a piped drain pan. These devices are highly recommended and are available from some plumbing supply wholesalers and retailers, and detect and react to leakage in various ways: • Sensors mounted in the drain pan that trigger an alarm or turn off the incoming water to the water heater when 1. Select a location indoors as close as practical to the vent terminal or location to which the water heater vent piping is going to be connected, and as centralized with the water piping system as possible. 2. A pressure-reducing valve and/or an expansion tank may be required for installations where the water pressure is high. The pressure-reducing valve should be located on the supply to the entire house in order to maintain equal hot and cold water pressure. 3. Selected location must provide adequate clearances for servicing and proper operation of the water heater. 4. Avoid locations that could cause the water heater to freeze from outside air. 5. Selected location must provide access to a properly grounded electrical branch circuit. A dedicated circuit is preferred. Do not use a GFI outlet. leakage is detected. • Sensors mounted in the drain pan that turn off the water supply to the entire building when water is detected in the drain pan. • Water supply shut-off devices that activate based on the water pressure differential between the cold water and hot water pipes connected to the water heater. • Devices that will turn off the gas supply to a gas water heater while at the same time shutting off its water supply. AVOID AREAS WHERE FLAMMABLE LIQUIDS (VAPORS) ARE LIKELY TO BE PRESENT OR STORED (GARAGES, STORAGE AND UTILITY AREAS, ETC.): Flammable liquids (such as gasoline, solvents, propane (LP or butane, etc.) and other substances (such as adhesives, etc.)) emit fl ammable vapors which can be ignited by a gas water heater's igniter or main burner. The resulting fl ashback Important: Do not use an extension cord to connect the water heater to an electrical outlet. Important: The electrical controls used inside the gas control of this water heater are polarity sensitive. Ensure the electrical supply is connected correctly in the receptacle box. Failure to connect correctly will prevent the unit from functioning properly. Installation of the water heater must be accomplished in and fi re can cause death or serious burns to anyone in the area. Also, the water heater must be located and/or protected so it is not subject to physical damage by a moving vehicle. 12 www.americanwaterheater.com DANGER FLAMMBLE Flammable Vapors HANDLE INSTALLATION For ease of handling and carrying, plugs are provided in the side of the shroud that can be removed and pipe handles inserted (see Figure 4). Vapors from flammable liquids may explode and catch fire causing death or severe burns. Do not use or store flammable products such as gasoline, solvents or adhe sives in the same room or area near the water heater. Keep flammable products: 1. far away from heater, 2. in approved containers, 3. tightly closed and 4. out of children's reach. Water heater has a main burner and spark generator. The spark generator: 1. can be triggered at any time and 2. the spark will ignite flammable vapors. Vapors: 1. cannot be seen, 2. are heavier than air, 3. go a long way on the floor and 4. can be carried from other rooms to the the electodes by air currents. • Remove plastic plugs from shroud side panels. • Screw a short length of 3/4" NPT pipe into the sides of the water heater. • Use the handles to move the water heater to the desired location. • Remove the handles. • Reinstall the plastic plugs in the shroud side panels. Handle Handle FIGURE 4 Installation: Do not install the water heater where flammable products will be stored or used. This water heater must not be installed directly on carpeting. Carpeting must be protected by metal or wood panel beneath the appliance extending beyond the full width and depth of the appliance by at least 3in. (7.6cm) in any direction, or if the appliance is installed in an alcove or closet, the entire fl oor must be covered by the panel. Failure to heed this warning may result in a fi re hazard. www.americanwaterheater.com 13 When installing the heater, consideration must be given to Remove the right side panel 1. proper location. Location selected should be as close to the wall as practicable and as centralized with the water 2. piping system as possible. 3. 4. Use a screwdriver to remove the screw from the bottom, front of the right side panel. Remove the three screws from the right side panel towards the rear of the unit. Remove the screw from the top of the unit. Push the panel back and lift out. Remove the left side panel 1. 2. FIGURE 5 3. 4. Minimum clearances between the water heater and combustible construction are 0 in. at the sides and rear, Use a screwdriver to remove the screw from the bottom, front of the left side panel. Remove the three screws from the left side panel towards the rear of the unit. Remove the screw from the top of the unit. Push the panel back and lift out. 0 in. (0cm) from the front and 2 in. (5.08cm) from the top (see Figure 5). If clearances stated on the heater differ from these distances, install water heater according to clearances stated on the heater. Adequate top clearance of 24 in. (61cm) for servicing this appliance, such as changing the anodes etc., should be considered before installation. A minimum front clearance of 20 in. (51cm) and 10 in. (26cm) of side clearance must be allowed for access to replaceable parts. EARTHQUAKE ZONES In Earthquake Zones the water heater must be braced, anchored, or strapped to avoid moving during an earthquake. Contact local utilities for code requirements in your area. The Spacemaker® TSE25 Bear Claw™ Water Heater Strap is suitable for bracing the Hybrid water heater. Follow the manufacturer's instructions for installing the braces. Be sure to wear protective goggles and gloves when handling any kind of sheet metal product. Tabs have been provided on each side of the rear portion of the shroud. The top and bottom of each tab must be cut and gently bent "inwards" thus allowing the straps to exit the shroud (see Figure 9). In order to access the tabs and install the earthquake straps it is necessary to remove the top, front and side panels of the shroud as follows (see Figures 6 - 8): Door opening Top Casing (Front) Door Lock FIGURE 6 Access To Door Pins Screws Unlock the door by rotating the lock counter-clockwise 1. with a wide, slot screwdriver. Release the top and bottom door pins by prying the 2. pins out, using a small screwdriver. Open the door (the door remains fastened to the left 3. side panel). Remove the top casing (front). Use a screwdriver to remove the six screws securing 1. the top casing. Lift up and remove casing top (front). 2. 14 www.americanwaterheater.com Screws Screws Top Casing (Front) FIGURE 7 Screws FIGURE 8 FIGURE 9 After the heater has been positioned and the earthquake straps have been installed, re-assemble the shroud in the reverse order. www.americanwaterheater.com 15 COMBUSTION AIR AND VENTILATION A gas water heater cannot operate properly without the correct amount of air for combustion. Do not install in a confi ned area such as a closet, unless you provide air as shown in the "Facts to Consider About Location" section. Never obstruct the fl ow of ventilation air. If you have any doubts or questions at all, call your gas supplier. Failure to provide the proper amount of combustion air can result in a fi re or explosion and cause death, serious bodily injury, or property damage. FIGURE 10 If this water heater will be used in beauty shops, barber shops, cleaning establishments, or self-service laundries with dry cleaning equipment, it is imperative that the water heater(s) be installed so that all air for combustion and ventilation is taken from outdoors. Note: Vent length should be long enough that the outside air will not freeze the water heater. Propellants of aerosol sprays and volatile compounds, (cleaners, chlorine based chemicals, refrigerants, etc.) in addition to being highly fl ammable in many cases, will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heater. The results can be hazardous, and also cause product failure. APPLIANCES IN UNCONFINED SPACES UNCONFINED SPACE is space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfi ned space. In unconfi ned spaces in buildings, infi ltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), additional air may need to be provided using the methods described in "Appliances in Confi ned Space" that follows." APPLIANCES IN CONFINED SPACES CONFINED SPACE is a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8cm per kW) of the aggregate input rating of all appliances installed in that space. When drawing combustion air from inside a building to a confi ned space, such a space should be provided with two permanent openings. ONE WITHIN 12 in. (30cm) OF THE ENCLOSURE TOP AND ONE WITHIN 12 in. (30cm) OF THE ENCLOSURE BOTTOM. Each opening should have a free area of 1 square inch per 1000 Btu/hr (22 cm2/kW) of the total input of all appliances in the enclosure, but not less than 100 square in. (645 cm2). If the confi ned space is within a building, air for combustion and ventilation must be obtained from outdoors. When directly communicating with the outdoors or communicating through vertical ducts, two permanent openings, located in the above manner, should be provided. Each opening should have a free area of not less than 1 square inch per 4000 Btu/hr (5.5 cm2/kW) of total input of all appliances in the enclosure. If horizontal ducts are used, each opening should have a free area of not less than 1 square inch per 2000 Btu/hr (11 cm2/kW) of the total input of all appliances in the enclosure. A. ALL AIR FROM INSIDE BUILDINGS: (See Figures 10 & 11) The confi ned space should be provided with two permanent openings communicating directly with an additional room(s) of suffi cient volume so that the combined volume of all spaces meets the criteria for an unconfi ned space. The total input of all gas utilization equipment installed in the combined space should be considered in making this determination. Each opening should have a minimum free area of 1 square inch per 1,000 Btu per hour (22 cm2/kW) of the total input rating of all gas utilization equipment in the confi ned space, but not less than 100 square in. (645 cm2). One opening should commence within 12 in. (30cm) of the top and one commencing within 12 in. (30cm) of the bottom of the enclosures. 16 www.americanwaterheater.com FIGURE 11 B. ALL AIR FROM OUTDOORS: (See Figures 12, 13 and 14) The confi ned space should be provided with two permanent openings, one commencing within 12 in. (30cm) of the top and one commencing within 12 in. (30cm) from the bottom of the enclosure. The openings should communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. 1. When directly communicating with the outdoors, each opening should have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure (see Figure 12). FIGURE 12 2. When communicating with the outdoors through vertical ducts, each opening should have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure (see Figure 13). 3. When communicating with the outdoors through horizontal ducts, each opening should have a minimum free area of 1 square inch per 2,000 Btu per hour (11 cm2/kW)) of total input rating of all equipment in the enclosure (see Figure 14). FIGURE 13 4. When ducts are used, they should be of the same cross-sectional area as the free area of the openings to which they connect. The minimum short side dimension of rectangular air ducts should not be less than 3 in. (7.6cm) (see Figure 14). FIGURE 14 5. Alternatively a single permanent opening may be used when communicating directly with the outdoors, or with spaces that freely communicate with the outdoors. The opening should have a minimum free area of 1 square inch per 3,000 BTU per hour (8.3 cm2/kW) of total input rating of all equipment in enclosure (see Figure 15). FIGURE 15 www.americanwaterheater.com 17 6. Louvers and Grilles: In calculating free area, consideration should be given to the blocking effect of louvers, grilles or screens protecting openings. Screens used should not be smaller than 1/4 in. (0.64cm) mesh. If the free area through a design of louver or grille is known, it should be used in calculating the size opening required to provide the free area specifi ed. If the design and free area is not known, it may be assumed that wood louvers will be 20-25 percent free area and metal louvers and grilles will have 60-75 percent free area. Louvers and grilles should be fi xed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation. 7. Special Conditions Created by Mechanical Exhausting or Fireplaces: operation of exhaust fans, ventilation systems, clothes dryers or fireplaces may create conditions requiring special attention to avoid unsatisfactory operation of installed gas utilization equipment. CHEMICAL VAPOR CORROSION CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS. SUCH CORROSION MAY RESULT IN FAILURE AND RISK OF ASPHYXIATION. Spray can propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium and sodium chloride (water softener salt), waxes, and process chemicals are typical compounds which are potentially corrosive. Do not store products of this sort near the heater. Also, air which is brought in contact with the heater should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outside sources. The limited warranty is voided when failure of water heater is due to a corrosive atmosphere. (See limited warranty for complete terms and conditions). WATER PIPING HOTTER WATER CAN SCALD: Water heaters are intended to produce hot water. Water heated to a temperature which will satisfy space heating, clothes washing, dish washing, cleaning and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the physically or developmentally disabled. If anyone using hot water fi ts into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap, then you must take special precautions. In addition to using the lowest possible temperature setting that satisfi es your hot water needs, a means such as a *mixing valve, should be used at the hot water taps used by these people or at the water heater (see Figure 3). Valves for reducing point of use temperature by mixing cold and hot water are also available: Consult a Qualifi ed Installer or Service Agency. Follow manufacturer's instructions for installation of the valves. Before changing the factory setting on the thermostat, read the "Temperature Regulation" section in this manual. This water heater should not be connected to any heating systems or component(s) used with a non-potable water heating appliance. All piping components connected to this unit should be suitable for use with potable water. Toxic chemicals, such as those used for boiler treatment should not be introduced into this system. When the system requires water for space heating at temperatures higher than required for domestic water purposes, a mixing valve must be installed. Please refer to Figure 3 for suggested piping arrangement. CLOSED WATER SYSTEMS Water supply systems may, because of code requirements or such conditions as high line pressure, among others, have installed devices such as pressure reducing valves, check valves, and back fl ow preventers. Devices such as these cause the water system to be a closed system. THERMAL EXPANSION As water is heated, it expands (thermal expansion). In a closed system, the volume of water will increase. As the volume of water increases, there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the 18 www.americanwaterheater.com limited warranty. Thermal expansion can also cause intermittent temperature-pressure relief valve operation: water discharged from the valve due to excessive pressure build up. The temperature-pressure relief valve is not intended for the constant relief of thermal expansion. This condition is not covered under the limited warranty. A properly-sized thermal expansion tank should be installed on all closed systems to control the harmful effects of thermal expansion. Contact a plumbing service agency or your retail supplier regarding the installation of a thermal expansion tank. NOTE: If using copper tubing, solder tubing to an adapter before attaching the adapter to the water heater connections. Do not solder the water lines directly to the water heater connections. It will harm the dip tube and damage the tank. SHUT-OFF VALVE HARD WATER We highly recommend installing water fi ltering system or a water softener before the water heater system. If you are installing a water fi ltering system use a 5 micron fi lter to reduce particles that can potentially cause nuisance shutdown problems and prolong the maintenance of the water heater's inlet fi lter. A water softener can affect the life of the anode installed in this water heater. Refer to "Anode Rod Inspection" section in this manual. Clean the fi lter on the water inlet as frequently as required by the quality of your local water. Refer to "Cleaning The Inlet Water Filter" section of this manual. One additional fi lter is supplied with your water heater. TEMPERATURE-PRESSURE RELIEF VALVE COLD WATER INLET TEMPERED POTABLE WATER MIXING VALVE (OPTIONAL) PIPE INSULATION (RECOMMENDED) Rear View FIGURE 16 This heater is provided with a properly certifi ed combination temperature - pressure relief valve by the manufacturer. The valve is certifi ed by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief Valves for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4, and the code requirements of ASME. If replaced, the valve must meet the requirements of local codes, but not less than a combination temperature and pressure relief valve certifi ed as indicated in the above paragraph. The valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 psi = 1,035 kPa) and a discharge capacity not less than the water heater Btu/hr input rate NOTE: To protect against untimely corrosion of hot and cold water fi ttings, it is strongly recommended that di-electric unions or couplings be installed on this water heater when connected to copper pipe (see Figure 3 also). Figures 3 and 16 show the typical attachment of the water piping to the water heater. The water heater is equipped with 3/4" NPT water connections. as shown on the water heater's rating plate. For safe operation of the water heater, the relief valve must not be removed from its designated opening nor plugged. www.americanwaterheater.com 19 The temperature-pressure relief valve must be installed directly into the fi tting of the water heater designed for the relief valve. Must terminate a maximum of 6 in. (15cm) above a fl oor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 ft. (9.14m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve (see Figures 3 & 19). No valve or other obstruction is to be placed between the relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6 in. (15cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water fl ow may cause property damage. The Discharge Pipe: • Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions. • Shall not be plugged or blocked. • Shall be of material listed for hot water distribution. • Shall be installed so as to allow complete drainage of both the temperature-pressure relief valve, and the discharge pipe. • Shall terminate a maximum of 6 in. (15cm) above a fl oor drain or external to the building. In cold climates, it is recommended that the discharge line be terminated at an adequate drain inside the building. • Shall not have any valve between the relief valve and tank. The temperature-pressure relief valve must be manually operated at least once a year, (see Figure 17). Caution should be taken to ensure that (1) no one is in front of or around the outlet of the temperature-pressure relief valve discharge line, and (2) the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot. FIGURE 17 If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions, and replace the temperature-pressure relief valve with a new one. T&P Valve and Pipe Insulation (if supplied) Remove insulation for T&P valve and pipe connections from carton. FIGURE 18 Fit pipe insulation over the incoming cold water line and the hot water line. Make sure that the insulation is against the top cover of the heater. Fit T&P valve insulation over valve. Make sure that the insulation does not interfere with the lever of the T&P valve. Secure all insulation using tape. 20 www.americanwaterheater.com GAS PIPING Make sure gas supplied is same type listed on model rating plate. The inlet gas pressure must not exceed 14 in. WC (3.5 kPa) for natural and propane gas (L.P.). The minimum inlet gas pressure shown on rating plate is that which will permit fi ring at rated input. All gas piping must comply with local codes and ordinances or with the National Fuel Gas Code (ANSI Z223.1/ NFPA 54). Copper or brass tubing and fi ttings (except tin lined copper tubing) should not be used. If the gas control valve is subjected to pressures exceeding 1/2 psi (3.5 kPa), the damage to the gas control valve could result in a fi re or explosion from leaking gas. If the main gas line shut-off serving all gas appliances is used, also turn "off" the gas at each appliance. Leave all gas appliances shut "off" until the water heater installation is complete. A gas line of suffi cient size must be run to the water heater. Consult the current edition of National Fuel Gas Code (ANSI Z223.1/NFPA 54) and your gas supplier concerning pipe size. There must be: • A readily accessible manual shut off valve in the gas supply line serving the water heater, and • A drip leg (sediment trap) ahead of the gas control valve to help prevent dirt and foreign materials from entering the gas control valve. • A fl exible gas connector or a ground joint union between the shut off valve and control valve to permit servicing of the unit. The appliance and its gas connections must be leak tested before placing the appliance in operation. Use a leak test solution, not a match or open fl ame. NOTE: An alternate location for the gas line entry is possible. Drill a suitable hole centered on the crosshairs on the left side panel. Use pipe joint compound or Tefl on tape marked as being resistant to the action of petroleum [Propane (L.P.)] gases. The appliance and its gas connection must be leak tested before placing the appliance in operation. The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of 1/2 psi (3.5 kPa). It shall be isolated from the gas supply piping system by closing its individual manual shut-off valve during the pressure testing, the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa) is considered isolated. IMPORTANT: MAKE SURE THE GAS LINE IS PIPED WITH HARD PIPE. AVOID FLEX LINE CONSTRUCTION FOR GAS DUE TO POSSIBLE GAS FLOW PROBLEMS. SEDIMENT TRAPS A sediment trap shall be installed as close to the gas inlet of the water heater as practical at the time of water heater installation. The sediment trap shall be either a tee fi tting with a capped nipple in the bottom outlet or other device recognized as an effective sediment trap. Contaminants in the gas lines may cause improper operation of the gas control valve that may result in fi re or explosion. Before attaching the gas line be sure that all gas pipe is clean on the inside. To trap any dirt or foreign material in the gas supply line, a drip leg (sometimes called www.americanwaterheater.com 21 a sediment trap) must be incorporated in the piping. The drip leg must be readily accessible. Install in accordance with the "Gas Piping" section. Refer to the current edition of the National Fuel Gas Code (ANSI Z223.1/NFPA 54). GAS LINE PURGING Air may be present in the gas lines and could prevent the burner from lighting on initial start-up. The gas lines should be purged of air by a qualifi ed service technician after installation of the gas piping system. HIGH ALTITUDE INSTALLATIONS WARNING Breathing Hazard - Carbon Monoxide Gas • Special consideration must be taken with installations above 11,000' (3,352m). • Please contact an AO Smith qualified service agent to obtain proper setup and instructions before lighting. • Failure to implement the proper setup will result in improper and inefficient FLOODING/FREEZING If this water heater has been exposed to flooding, freezing, fi re or any unusual condition, do not put it into operation until it has been inspected and approved by a qualifi ed service technician. These conditions can result in unseen internal damage and are not subject to warranty coverage. FILLING THE WATER HEATER Never use this water heater unless it is completely full of water. To prevent damage to the tank, the tank must be fi lled with water. Open the nearest hot water faucet to allow air to escape. Water must fl ow from the hot water faucet before turning "ON" gas to the water heater. To fi ll the water heater with water: 1. operation of the appliance resulting in production of increased levels of carbon monoxide gas in excess of the safe limits which could result in serious 2. personal injury or death. Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. 3. The heater is set at the factory to operate at altitudes from sea level to 3,500 ft. (1,067m). Accessory kits are available to allow the heater to operate at altitudes higher than 3,500 4. ft. (1,067m). These accessory kits are listed in the table below. Instructions for installing these accessories are Close the water heater drain valve by turning the handle to the right (clockwise). The drain valve is on the lower front of the water heater. Open the cold water supply valve to the water heater tank. NOTE: The cold water supply valve must be left open when the water heater is in use. To insure complete fi lling of the tank, allow air to exit by opening the nearest hot water faucet. Allow water to run until a constant fl ow is obtained. This will let air out of the water heater and the piping. Check all water piping and connections for leaks. Repair as needed. included in the kits. Altitude ft (m) Kit # 3,501 - 6,500 (1,067 -1,981) 9007439005 6,501 - 8,500 (1,981 - 2,591) 9007440005 8,501 - 11,000 (2,591 - 3,352) 9007441005 Rated inputs are suitable up to 11,000 ft. (3,352m) elevation. Consult the factory for installation at altitudes over 11,000 ft. (3,352m). WARNING: THIS HIGH EFFICIENCY WATER HEATER IS CERTIFIED FOR USE AT AN ALTITUDE OF 11,000 Ft. (3,352 METERS). HOWEVER, FOR USE AT ALTITUDES OVER 3,500 Ft. (1,067m) THE PCB MUST BE CHANGED. Some gas utility companies derate their gas for altitude, making it unnecessary to modify the water heater for high altitude installations. Call the local gas or utility company to verify BTU content. VENTING 22 www.americanwaterheater.com VENT PIPE TERMINATION NOT RECOMMENDED: PREFERRED PRACTICE: Instructions on proper installation through a sidewall are provided in Figures 31. Plan the vent system layout so that proper clearances are maintained from plumbing and wiring. Vent pipes serving power vented appliances are classifi ed by building codes as "vent connectors". Required clearances from combustible materials must be provided in accordance with information in this manual under FACTS STREET ELBOW NORMAL ELBOW 6 in. (15 cm) min. BACK TO BACK ELBOWS TO CONSIDER ABOUT LOCATION AND INSTALLING THE WATER HEATER, and with the National Fuel Gas Code and local codes. PLANNING THE VENT SYSTEM Plan the route of the vent system from the exhaust elbow to the planned location of the vent terminal. 1. Layout total vent system to use a minimum of vent pipe and elbows. 2. This water heater is capable of venting fl ue gases a maximum distance equivalent to 50 ft. (15.2m) of 2 in. pipe or 100 ft. (30.5m) of 3 in. pipe. The use of elbows reduces the maximum distance (see Table 1). NOTE: The lengths of pipe listed are exclusive of the termination. The termination elbow, with an installed screen, is required and uses the equivalent of 7 ft. (2.1m) of vent pipe length. Therefore, the remainder of the vent system must not exceed the lengths listed. NOTE: Do NOT use Cellcore venting (PVC outer layer, foamcore-type material for middle layer, and then PVC inside layer). 90° SHORT SWEEP ELBOW (MORE RESTRICTIVE) FIGURE 19 90° LONG SWEEP ELBOW (LESS RESTRICTIVE) Number of 90° Elbows Maximum vent length for 2 in. pipe ft. (m) Maximum vent length for 3 in. pipe ft. (m) Short Radius Elbow Long Radius Elbow Short Radius Elbow Long Radius Elbow 1 43 (13.1) 45 (13.7) 93 (28.4) 95 (28.9) 2 36 (10.9) 40 (12.2) 86 (26.2) 90 (27.4) 3 29 (8.8) 35 (10.6) 79 (24.0) 85 (25.9) 4 22 (6.7) 30 (9.1) 72 (21.9) 80 (24.4) 5 15 (4.5) 25 (7.6) 65 (19.8) 75 (22.8) TABLE 1 VENT LENGTH LESS THAN OR EQUAL TO 20 EQUIVALENT FEET (6.1m) USE THIS SCREEN. VENT LENGTH GREATER THAN 20 EQUIVALENT FEET (6.1m) USE THIS SCREEN. 3. The exhaust elbow assembly comes with a straight section of 2 in. pipe installed. To continue the vent FIGURE 20 The fi rst step is to determine where the vent pipe will terminate (see Figures 24, 29 & 31). The vent may terminate through a sidewall as shown in Figure 24 or through the roof as shown in Figure 29. The vent system must terminate so that proper clearances are maintained as cited in local codes or the current edition of the National Fuel Gas Code, (ANSI Z223.1, 12.9.1 through 12.9.4). system, a rubber coupling must be attached. The venting must extend 6 in. (15cm) vertically from the top of the heater before installing an elbow. If using 2 inch vent pipe: Install the rubber coupling and gear clamps (supplied) at the end of the section of vent pipe installed on the heater. Continue building the vent system, or connect the existing vent system to the coupling. The total vent system must not exceed the lengths discussed above, where each (short radius) elbow is equal to 7 equivalent feet (2.1m) of straight pipe. The elbow and rodent screen supplied in the vent kit must be used as the vent termination. www.americanwaterheater.com 23 TERMINATION ELBOW RODENT SCREEN NOTE: VENT PIPE MUST BE SUPPORTED EVERY 4 ft. (1.2m). TO PREVENT VIBRATION, USE ISOLATION PADS WHEN ATTACHING STRAPS TO FLOOR JOISTS, WALLS OR CEILINGS. STRAP 45° ELBOW 90° ELBOW (INSTALL INTO ELBOW) GROUND LEVEL OR MAXIMUM SNOW LINE* Example for calculating equivalent feet. Section "A" . . . . 0.5 ft. . . (0.15m) 90° elbow . . . . . 7.0 ft. . . (2.13m) Section B . . . . . 1.0 ft. . . (0.31m) 45° elbow . . . . . 4.0 ft. . . (1.21m) Section C . . . . . 1.5 ft. . . (0.46m) 45° elbow . . . . . 4.0 ft. . . (1.21m) Section D . . . . . 15.0 ft. . (4.57m) Total Equivalent 33.0 ft. . (10.04m) Based on this example use the (fully open) rodent screen for vent length greater than 20 equivalent ft. (6.1 equivalent metres). Vent piping must slope up from heater to termination a minimum of 1/8 in. (0.3cm) rise per 4 ft. (1.2m) of vent piping 6 in. (15cm) MIN. If using 3 inch vent pipe: FIGURE 21 If the water heater is being installed as a replacement Install the rubber reducing coupling (2 in. to 3 in.) and gear clamps (supplied) at the end of the section of vent pipe installed on the heater. Continue building the vent system, or connect the existing vent system to the coupling. The total system must not exceed the equivalent pipe lengths discussed above where each (long radius) elbow is equal to 5 ft. (1.5m) of 3 in. diameter straight vent pipe. The elbow and rodent screen supplied in the vent kit must be used as the vent termination. NOTE: This unit can be vented with PVC pipe materials (DWV ASTM-D2665; Schedule 40, 80, 120 ASTM D1785; or SDR Series ASTM-D2241), CPVC pipe materials (CPVC41 ASTM-D2846; Schedule 40, 80 ASTM-F441; or SDR Series ASTM-F442), ABS pipe materials (Schedule 40 DWV ASTM-D2661). The fittings, other than the TERMINATION should be equivalent to PVC-DWV fi ttings meeting ASTM D-2665 (Use CPVC fi ttings, ASTM F-438 for CPVC pipe and ABS fi ttings, ASTM D-2661/3311 for ABS pipe). If CPVC or ABS pipe and fi ttings are used, then proper cement must be used for all joints, including joining the pipe to Termination (PVC Material). If local codes do not allow the use of the PVC termination when a material other than PVC is used for venting, then an equivalent fi tting of that material may be substituted if the screen in the PVC terminal is removed and inserted into the new fi tting. This water heater is supplied with a 45 degree termination elbow that is a special fi tting that must be used with the appliance. PVC Materials should use ASTM D-2564 Grade Cement; CPVC Materials should use ASTM F-493 Grade Cement and ABS Materials should use ASTM D-2235 Grade Cement. for an existing power vented heater in pre-existing venting, a thorough inspection of existing venting system must be performed prior to any installation work. Verify that correct material as detailed above has been used, and that the minimum or maximum vent lengths and terminal location as detailed in this manual have been met. Carefully inspect the entire venting system for any signs of cracks or fractures, particularly at joints between elbows and other fi ttings and straight runs of vent pipe. Check system for signs of sagging or other stresses in joints as a result of misalignment of any components in the system. If any of these conditions are found, they must be corrected in accordance with the venting instructions in this manual before completing installation and putting the water heater into service. NOTE: (A.) For water heaters in locations with high ambient temperatures (above 100°F (38°C)) it is recommended that CPVC or ABS pipe and fi ttings be used. (B.) A 22.5 degree elbow (2 in. vent pipe) or a 45 degree elbow (3 in. vent pipe) with an installed screen VENT TERMINAL must be used in all cases. 4. There will be some installations where condensate will be formed in the horizontal runs of the vent system. This condensate will run into the condensate trap. The water heater is shipped with a condensate tube that attaches to the condensate trap. No other tee or fi tting is required. 24 www.americanwaterheater.com CONDENSATE This water heater is a condensing unit and requires a drain to be located in close proximity to allow the condensate to drain safely. The condensate drains from the unit at the exhaust tee located at the bottom of the unit (see Figure 22). Condensate from this water heater is mildly acidic. Please note that some local codes require that condensate is treated by using a pH neutralizing fi lter prior to disposal. Caution must be used to ensure that the drain is free and clear of debris and will not allow backfl ow through the condensate tube. Consideration must be given to avoid freezing of the condensate lines which could result in excessive build up of condensate inside the water heater. Waterproof heat tape may be required to prevent freezing of the condensate lines. Please ensure that the outlet of the condensate drain does not create a slippery condition which could lead to personal injury. To operate properly and prevent exhaust gases from EXHAUST ELBOW VENTING BARBED FITTING CONDENSATE TRAP DRAIN PAN - ROUTE TO SUITABLE DRAIN CONDENSATE TUBE - SLOPE TO SUITABLE DRAIN NOTE: THE CONDENSATE TUBE MUST BE BELOW EXHAUST ELBOW. FIGURE 22 escaping through the condensate trap, the trap must contain some water. Before being started for the fi rst time, water must be added to the trap. Remove the condensate tube (if installed) and add water to the trap through the hole for the condensate tube until it fl ows from the hole. (Re)install the condensate tube. CONDENSATION WARNING: THIS WATER HEATER IS A CONDENSING UNIT AND REQUIRES A DRAIN TO BE LOCATED IN CLOSE PROXIMITY TO ALLOW CONDENSATE TO DRAIN SAFELY. THE CONDENSATE DRAINS FROM UNIT AT THE EXHAUST ELBOW LOCATED AT BOTTOM OF UNIT. NOTE: IT IS IMPORTANT THAT THE CONDENSATE TUBE NOT BE ELEVATED ABOVE THE CONDENSATE TRAP OUTLET (SEE FIGURE 22). CONDENSATE BUILD-UP WILL BLOCK THE EXHAUST OUTLET, WHICH WILL CAUSE IMPROPER OPERATION. WITH SOME INSTALLATIONS IT IS RECOMMEND TO INSTALL A CONDENSATE PUMP. NOTE: Barbed fi tting not required if hard piping is used to drain condensate. INSTALLATION OF VENT SYSTEM Before beginning installation of piping system thoroughly read the "Vent Pipe Preparation" section of this manual. If you are installing your system so that it vents through roof, please refer to the section titled "Installation Of Vertical Vent System". Ensure the vent length is long enough that the outside air will not cause the water heater to freeze. VENT TERMINAL INSTALLATION, SIDEWALL 1. Install the vent terminal by using the cover plate as a template to mark the hole for the vent pipe to pass through the wall. BEWARE OF CONCEALED WIRING AND PIPING INSIDE THE WALL. 2. If the Vent Terminal is being installed on the outside of a fi nished wall, it may be easier to mark both the inside and outside wall. Align the holes by drilling a hole through the center of the template from the inside through to the outside. The template can now be positioned on the outside wall using the drilled hole as a centering point for the template. 3. A) MASONRY SIDE WALLS Chisel an opening approximately 1/2 in. (1.3cm) larger than the marked circle. B) WOODEN SIDE WALLS Drill a pilot hole approximately 1/4 in. (0.64cm) outside of the marked circle. This pilot hole is used as a starting point for a saws-all or sabre saw blade. Cut around the marked circle staying approximately 1/4 in. (0.64cm) outside of the line. (This will allow the vent to easily slide through the opening. The resulting gap will be covered up by the Vent Terminal cover plate.) Repeat this step on inside wall if necessary. www.americanwaterheater.com 25 SEQUENCE OF INSTALLATIONS Cut a length of PVC pipe about 3.5 in. (9cm) longer than the wall thickness at the opening. Glue the vent terminal to this section of pipe. Slide the wall plate over the pipe to stop against the vent terminal. Place a bead of caulking (not supplied) around the gap between the pipe and cover plate. Apply enough to fi ll some of the gap between the pipe and wall. Place some of the caulking on the back of the plate to hold it against the wall after installation. If the vent pipe is installed up to the wall, with a coupling on the end against the wall opening, the pipe with the vent terminal can be prepared for gluing before inserting through the wall. Slide the pipe through the wall and insert into the coupling on the other side of the wall, making sure that the vent terminal ends up pointed in the correct position (see Figure 23). FIGURE 23 INSTALLATION SEQUENCE For installations in the City of Los Angeles, California Category IV PVC Pipe such as that manufactured by Brownline Pipe Company, must be used as vent pipe material. CAUTION Vent terminals supplied with heater must be used. NOTE: BEFORE BEGINNING INSTALLATION OF ANY VENT PIPE READ THE VENT PIPE MANUFACTURER'S INSTALLATION INSTRUCTIONS. 1. After the points of termination have been determined, use the cover plates as templates to mark the holes for the vent pipes to be inserted through the wall. BEWARE OF CONCEALED WIRING AND PIPING INSIDE OF WALL. If the vent terminals are being installed on the outside of a fi nished wall, it may be easier to mark both the inside and outside wall. Align the holes by drilling a hole through the center of the template from the inside through to the outside. The template can now be positioned on the outside wall using the drilled holes as a centering point for the template. A. MASONRY SIDE WALLS Chisel an opening approximately 1/2 in. (1.3cm) larger than the marked circle. B. WOODEN SIDE WALLS Drill a pilot hole approximately 1/4 in. (0.64cm) outside of the marked circle. This pilot hole is used as a starting point for a saws-all or sabre saw blade. Cut around the marked circle staying approximately 1/4 in (0.64cm) outside of the line. (This will allow the vent pipe to easily slide through the opening. The resulting gap will be covered by the vent terminal cover plates.) Repeat this step on the inside wall if necessary. 2. Cut a length of 3 in. PVC pipe about 3.5 in. (9cm) longer than the wall thickness at the opening. 3. Glue the intake vent terminal to the section of the pipe. 4. Slide the wall plate over pipe to stop against intake vent terminal. 5. Place a bead of caulking (not supplied) around the gap between the pipe and the wall. Place some of the caulking on the back of the plate to hold it against the wall after installation. 6. If the vent pipe is installed up to the wall, with a coupling on the end against the wall opening, the pipe with the vent terminal can be prepared for gluing before inserting through the wall. Slide the pipe through the wall and insert into coupling on the other side of the wall, making sure that the vent terminal ends up pointed in the correct position (see Figure 24). FIGURE 24 26 www.americanwaterheater.com 6 in. (15 cm) MIN. LENGTH ATTACH 45° TERMINATION ELBOW RODENT SCREEN (INSTALL SEALANT VENT PIPING TO BE SLOPED (DOWN) TOWARD HEATER TO PREVENT WATER ATTACH 45° TERMINATION ELBOW RODENT SCREEN (INSTALL INTO ELBOW) BRACKET EQUIVALENT VENT LENGTH MEASURED FROM THIS POSITION 12 in. FROM COLLECTING. SEALANT 12 in. (30 cm) min. INTO ELBOW) SEALANT (30 cm) min. VENT RISER GROUND LEVEL* * WHERE SNOW COVER IS NORMAL DURING WINTER, ENSURE SUFFICIENT VENT CLEARANCE TO PREVENT BLOCKAGE OR ICE BUILDUP. GROUND LEVEL* SEALANT VENT PIPING TO BE SLOPED (DOWN) TOWARD HEATER TO FIGURE 25 INSTALLATION OF VENT SYSTEM, SIDEWALL * WHERE SNOW COVER IS NORMAL DURING WINTER, ENSURE SUFFICIENT VENT CLEARANCE TO PREVENT BLOCKAGE OR ICE BUILDUP. FIGURE 27 PREVENT WATER FROM COLLECTING. With the route of the venting system and selection of materials completed, as discussed in the section of this manual titled "Planning The Vent System", the through the wall vent terminal in place and the fi rst section of piping, up to fi rst elbow, installed at the rubber coupling, it is time to complete the installation of the venting system for the sidewall installation. FIGURE 26 Before completing the installation of the venting system be sure to read the sections of this manual discussing the proper method of cutting and cementing PVC pipe and fi ttings in the "Vent Pipe Preparation" section. It is recommended that the completion of the venting system start at the rubber coupling and run to the coupling on the inside wall of the vent terminal (see Figure 23). The vent system piping should be supported every 5 ft. (1.5m) of vertical run and every 3 ft. (91cm) of horizontal run. All piping and fi ttings must be joined by the proper procedures as described under: VENT PIPE PREPARATION. INSTALLATION OF VERTICAL VENT SYSTEM A proper fl ashing or "BOOT" should be used to seal the pipe where it exits the roof. The total vent system should not exceed the equivalent feet of pipe as listed in Table 1. Provide support for all pipe protruding through the roof. All piping should be properly secured. The vent system piping should be supported every 5 ft. (1.5m) of vertical run and every 3 ft. (91cm) of horizontal run. All piping and fi ttings must be joined by the proper procedures as described under: VENT PIPE PREPARATION. www.americanwaterheater.com 27 FIGURE 28 3 in. (7.6cm) MIN. LENGTH TERMINATION MAY BE 45° ELBOW OR A "T" ELBOW RODENT VENT PIPE PREPARATION 1. INITIAL PREPARATION. A. Make sure the solvent cement you are planning to use is designed for the specifi c application you are attempting. B. Know the physical and chemical characteristics and limitations of the PVC and CPVC piping materials that you are about to use. C. Know the reputation of your manufacturer and their products. D. Know your own qualifications or those of your contractor. The solvent welding technique of joining PVC and CPVC pipe is a specialized skill just as any other pipe fi tting technique. E. Closely supervise the installation and inspect the fi nished job before start-up. F. Contact the manufacturer, supplier, or competent consulting agency if you have any questions about the application or installation of PVC and CPVC pipe. G. Take the time and effort to do a professional job. Shortcuts will only cause you problems and delays in start-up. By far, the majority of failures in PVC and CPVC systems are the result of shortcuts and/or improper joining techniques. 2. SELECTION OF MATERIALS. • Cutting Device - Saw or Pipe Cutter. • Deburring Tool, Knife, File, or Beveling Machine (2 in. and above). • Brush - Pure Bristle. • Rag - Cotton (Not Synthetic). • Primer and Cleaner. A VENT USED IN A SPECIAL VENTING SYSTEM WITH POSITIVE VENT PRESSURE AND PASSING THROUGH A ROOF SHALL EXTEND AT LEAST 450mm (18 in.) ABOVE THE HIGHEST POINT WHERE IT PASSES THROUGH THE ROOF SURFACE AND ANY OTHER OBSTRUCTION WITHIN A HORIZONTAL DISTANCE OF 450mm (18 in.). A VERTICAL VENTING SYSTEM MUST BE SUPPORTED EVERY 1.5m (5 ft.). FIGURE 29 IMPORTANT 18 in. (45cm) SCREEN (INSTALL INTO ELBOW) ROOF LINE • Solvent Cement - PVC for PVC Components and CPVC for CPVC Components. • Containers - Metal or Glass to hold Primer and Cement. Select the type of PVC or CPVC materials to be used on the basis of their application with respect to chemical resistance, pressure rating, temperature characteristics, etc. • Insertion Tool - Helpful for larger diameter pipe and fi ttings 6 in. (15cm) and above. The vent system must terminate so that proper clearances are maintained as cited in local codes or the current edition of the National Fuel Gas Code (ANSI Z223.1) and as listed below: 1. Vent Termination must extend a minimum of 18 in. (46cm) above roof or 18 in. (46cm) above the anticipated snow level to prevent blockage of the vent termination, as shown in Figures 28 and 29. 28 www.americanwaterheater.com PRIMER It is recommended that Tetrahydrofuran (THF) be used to prepare the surfaces of pipe and fi ttings for solvent welding. Do not use water, rags, gasoline or any other substitutes for cleaning PVC or CPVC surfaces. A chemical cleaner such as MEK may be used. CEMENT The cement should be a bodied cement of approximately 500 to 1600 centipoise viscosity containing 10-20% (by weight) virgin PVC material solvated with tetrahydrofuran (THF). Small quantities of dimethyl formamide (DMF) may be included to act as a retarding agent to extend curing time. Select the proper cement; Schedule 40 cement should be used for Schedule 40 pipe. Never use all-purpose cements, commercial glues and adhesives or ABS cement to join PVC or CPVC pipe and fi ttings. APPLICATORS Select a suitable pure bristle type paint brush. Use a proper width brush or roller to apply the primer and cement (see chart below). Speedy application of cement is important due to its fast drying characteristics. IMPORTANT NOTE: A dauber type applicator should only be used on pipe sizes 2 in. and below. For larger diameter pipe, a brush or roller must be used. RECOMMENDED BRUSH* SIZE FOR PRIMER AND CEMENT APPLICATIONS Nominal Pipe (IPS) Size Brush Width 2 1.5 in. (3.8cm) 3 1.5"-2.5 in. (3.8cm - 6.4cm) *USE ONLY NATURAL BRISTLE 3. MAKING THE JOINT. A. Cutting Pipe must be squarely cut to allow for the proper interfacing of the pipe end and the fi tting socket bottom. This can be accomplished with a miter box saw or wheel type cutter Wheel type cutters are not generally recommended for larger diameters since they tend to fl are the corner of the pipe end. If this type of cutter is used, the fl are on the end must be completely removed. NOTE: Power saws should be specifi cally designed to cut plastic pipe. STEP A B. Deburring Use a knife, plastic pipe deburring tool, or fi le to remove burrs from the end of small diameter pipe. Be sure to remove all burrs from around the inside as well as the outside of the pipe. A slight chamfer (bevel) of about 10°-15° should be added to the end to permit easier insertion of the pipe into the end of the fi tting. Failure to chamfer the edge of the pipe may remove cement from the fi tting socket, causing the joint to leak. STEP B C. Test dry fi t of the joint Tapered fitting sockets are designed so that an interfaced fi t should occur when the pipe is inserted about 1/3 to 2/3 of the way into the socket. Occasionally, when pipe fi tting dimensions are at the tolerance extremes, it will be possible to fully insert dry pipe to the bottom of the fi tting socket. When this happens, a suffi cient quantity of cement must be applied to the joint to fi ll the gap between the pipe and fi tting. The gap must be fi lled to obtain a strong, leak-free joint. www.americanwaterheater.com 29 D. Inspection, cleaning, priming Visually inspect the inside of the pipe and fi tting sockets and remove all dirt, grease or moisture with a clean dry rag. If wiping fails to clean the surfaces, a chemical cleaner must be used. Check for possible damage such as splits or cracks and replace if necessary. Depth-of-entry Marking the depth of entry is a way to check if the pipe has reached the bottom of the fi tting socket in Step F. Measure the fi tting depth and mark this distance on the pipe O.D. You may want to add several inches to the distance and make a second mark as the primer and cement will most likely destroy your fi rst one. Apply primer to the surface of the pipe and fi tting socket with a natural bristle brush. This process softens and prepares the PVC or CPVC for the solvent cementing step. Move quickly and without hesitation to the cementing procedure while the surfaces are still wet with primer. E. Application of solvent cement • Apply the solvent cement evenly and quickly around the outside of the pipe at a width a little greater than the depth of the fi tting socket. • Apply a light coat of cement evenly around the inside of the fi tting socket. Avoid puddling. • Apply a second coat of cement to the pipe end. STEP E F. Joint assembly Working quickly, insert the pipe into the fi tting socket bottom and give the pipe or fi tting a 1/4 turn to evenly distribute the cement. Do not continue to rotate the pipe after it has hit the bottom of the fi tting socket. A good joint will have suffi cient cement to make a bead all the way around the outside of the fi tting hub. The fi tting will have a tendency to slide back while the cement is still wet so hold the joint together for about 15 seconds. Remove all excess cement from around the pipe and fi tting with a dry cotton rag. This must be done while the cement is still soft. The joint should not be disturbed immediately after the cementing procedure, and suffi cient time should be allowed for proper curing of the joint. Exact drying time is diffi cult to predict because it depends on variables such as temperature, humidity and cement integrity. For more specifi c information, you should contact your solvent cement manufacturer. STEP G CONNECTION TO VENT PIPE The vent system connects to the vent pipe with and elbow or rubber coupling. This coupling includes gear clamps. These connections must be properly seated and tightened to prevent the leakage of fl ue gases into the installation area. With 2 in. venting the straight rubber adapter is used for the connection to the vent pipe. With 3 in. venting a transition adapter is required to change from the 2 in. vent pipe to the 3 in. vent size. Clean and lightly sand the end of the vent piping that will connect to the rubber coupling. Loosen the upper clamp on the rubber adapter and insert the sanded end of the vent pipe and tighten the gear clamp. NOTE: Do not glue or seal in the rubber coupling. Check the venting system to ensure that there is no stress on the connection or the vent pipe which will create a twisting or bending. UPPER GEAR CLAMP LOWER GEAR CLAMP STEP F G. Cleanup and joint movement RUBBER COUPLING/ ADAPTER (2") U.S. POWER VENT RUBBER ADAPTER (2 in.to 3") FIGURE 30 30 www.americanwaterheater.com WARNING VENT HOOD(S) MAY BE EXTREMELY HOT DURING OPERATION. FIGURE 31 CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY/COLD AREAS, THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS RECOMMENDED. www.americanwaterheater.com 31 ELECTRICAL CONNECTIONS To put the heater into service after a successful calibration: 1. The water heater must be connected to a properly 2. grounded electrical branch circuit. A dedicated circuit is preferred. Do not use a GFI outlet. Refer to the rating plate attached to the water heater to 3. determine the electrical requirements for the heater. Ensure the circuit provided is correct for these requirements. 4. Important: Do not use an extension cord to connect the 5. water heater to an electrical outlet. 6. Important: The electrical controls used inside the gas control of this water heater are polarity sensitive. Ensure the electrical supply is connected correctly in the receptacle box. Failure to connect correctly will prevent the unit from functioning properly. When all the water, gas and venting connections have Unplug the power cord from the 120Vac/60Hz outlet Open (plastic) front door of the heater and remove the cover of the heat engine. The DIP switches are located on the PCB which is mounted on the right-hand side of the heat engine. Set DIP switch 4 in the normal (OFF or "up") position (see Figure 33a). Reinstall the front cover of the heat engine, close and latch the front door of the heater. Plug the power cord into the 120Vac/60Hz outlet. Press the Standby Button to turn on the heater and start the unit. been correctly made, fi ll the tank as directed in the section "FILLING THE WATER HEATER". When the tank has been fi lled, connect the electrical power DIP Switch 4 in normal mode ("OFF", "up") DIP Switch 4 in calibration mode ("ON", "down") FIGURE 33a and proceed with starting the water heater as directed in the "CALIBRATION" section. CALIBRATION The water heater must be calibrated as follows before being put into service. The Calibration Procedure examines and measures certain details of your installation and automatically sets some control parameters. Before starting the Calibration Procedure, the heater must be properly installed and connected to the water piping and the vent system. Ensure all panels, covers and doors are in place. To avoid a possible "end of call-for-heat" (and consequent interruption of the Calibration Procedure), a continuous water draw from the heater is recommended during the calibration. This procedure assumes that the heater is installed with The E36 "calibration error" occurs in the following situations: • Calibration switch (DIP switch 4) is in the calibrate (ON or "down") position and an "end call-for-heat" occurs before the Calibration Procedure is fi nished. • Calibration switch (DIP switch 4) is in the calibrate (ON or "down") position there is no "call-for-heat" within 6 minutes of turning on the power. • Calibration switch (DIP switch 4) is in the calibrate (ON or "down") position and the unit is calibrated but the DIP switch is not set to the normal (OFF or "up") within 6 minutes after the Calibration Procedure is fi nished. • Calibration switch (DIP switch 4) is in the normal (OFF or "up") position and the unit is not calibrated and 1 minute (or more) passes after turning on the power. If an E36 error message is displayed: 1. DIP switch 4 in the calibration (ON or "down") position 2. (see Figure 33a). 3. To calibrate the heater: Unplug the power cord from 120Vac/60Hz outlet. Open front door of the heater and remove the front cover of the heat engine. Check that (or set) DIP switch 4 is in the calibrate (ON Plug the power cord into a 120Vac/60Hz outlet. 1. 4. Press the Standby Button to turn on the heater and 2. initiate the Calibration Procedure. 5. 3. The Calibration Procedure will last about 6 minutes. Do or "down") position. Generate a 5 minute (minimum) water draw from the heater. Repeat the calibration procedure. not interrupt this procedure once it has started. After a successful calibration the heater will go into standby mode. During the calibration if the "call-for-heat" ends, the calibration was not completed and the E36 error message will be shown on the display. If this occurs, unplug the power cord and repeat steps 1 and 2. NOTE: If changes are made to the vent system or the heater is re-located, the Calibration Procedure must be repeated. 32 www.americanwaterheater.com OPERATING INSTRUCTIONS DISPLAY PANEL STANDBY LED (GREEN) TEMPERATURE UNITS-OF-MEASURE STANDBY-ON/OFF BUTTON NUMERIC DISPLAY UP (HOTTER) BUTTON MODE BUTTON KEY LOCK BURNER IN MODE LEDs (3) OPERATION FAULT INDICATOR FIGURE 33 DOWN (COLDER) BUTTON Changing the Standby Status When the Standby Button is pressed, the Status changes to normal operation and all the LEDs on the display will light up for a period of 1 second to verify operation. The button can toggle the status between Normal operation and Standby. Key Lock NOTE: This is a tamper resistant feature. The Key Lock is considered "On" or "Off": • Key Lock is turned "On" after one minute without a key press by the user. • Key Lock can then be turned "Off" for one minute by simultaneously pressing the "Up" Button and the "Down" Button for three seconds. When the keys are locked, the Temperature Set-point cannot be increased and the Operating Mode cannot be changed. The set-point may be decreased while the keys are locked. The On/Off Button is not affected by the Key Lock feature. All other buttons are "locked" when the Key Lock is "On". The "Key Lock" icon will be displayed if the water heater is either in the lock or unlock condition. The Icon is composed of 3 components, the base, a locked and an unlocked arc. Operating Modes Operating modes are: Boost (for peak demand), Energy Saver and Vacation. Three LEDs are used to indicate the Operating Mode. Vacation Mode: Yellow LED Energy Saver Mode: Green LED Boost Mode: Orange LED The Operating Modes have the following characteristics: Vacation mode: • Fixed temperature setting of 90°F (32°C) • Set-point Difference is 14°F (8°C) • Tank Set-point Differential is 22°F (12°C) Energy Saver mode: • Temperature range from 100°F to 135°F (38°C to 57°C) in increments of 1°F or 1°C • Set-point Difference is 14°F (8°C) • Tank Set-point Differential is 14°F (8°C) Boost mode: • Temperature ranges from 140°F to 158°F (60°C to 70°C) in increments of 1°F or 1°C • Set-point Difference is 14°F (8°C) • Tank Set-point Differential is 9°F (5°C) Switching between operating modes is done by pressing the "Mode" Button when the Key Lock is "Off". When a mode is active, the corresponding LED is turned on. Pressing the "Mode" button will cycle between the three possible modes of operation. www.americanwaterheater.com 33 Numeric Display Numeric information such as temperature set-point, maintenance codes and error codes are displayed using a large yellow LED display. Up and Down Buttons Two buttons (with "Up" and "Down" arrows) are used for adjusting the data on the display. Other secondary functions such as turning the Key Lock "Off", are described in other sections. Temperature Set-point change Two buttons (with "Up" and "Down" arrows) are used to adjust the desired temperature set-point. When the Temperature Set-point is displayed and the Key Lock Is "Off", pressing the Up Button will increase the set-point and pressing the Down button will decrease the set-point. NOTE: The Temperature Set-point cannot be adjusted beyond the limits of the current Mode selected. Burner in Operation When the burners are in operation and fl ame is detected by the fl ame sensor, the fl ame symbol is illuminated. Switching Between Units of Measure Switching between temperature units of measure (°F/°C). Two yellow LEDs will be used to light up the current unit mode, °F or °C. To switch units of measure, simultaneously press the "Mode" button and the "Up" button. Fault Indication A red fault LED (lighting a large red exclamation point) should be present on the display panel. Maintenance mode By simultaneously pressing the "Mode" and "down arrow" buttons for 3 seconds the unit will allow access to the maintenance mode. 34 www.americanwaterheater.com WIRING DIAGRAM c a V 0 2 1 r e m r e o s f u s F n l a r a T m r r e e h w T o N N N N E E P K K K K E E W W T T E E C C C C I I D D E E O O A A A A U U H H R R L L L L E E L L R R B B B B G R R B B G W B B W e 1 s F 1 u 4 56 3 2 11 2 F l c c a 2 a 3 4 e m V e J J 7 r S 0 s e J 2 R u 3 h 1 F T M r F e X w o P ) r r e r P m e r 6 o R w f 1 s o M 2 1 3 l n J r F a B BROWN r X e T t 4 ( i n g YELLOW r r I YELLOW e e 3 t 2 i w YELLOW n o J BLUE l g I B / 2 t 5 u RED O 1 2 4 3 1 1 J y r a p i GREEN l i m x u u P p A 3 ORANGE m M 1 u 2 1 J P ORANGE WHITE O O C C WHITE E E BLACK 9 6 3 / BLUE s 2 e p o 1 v r l P 2 5 8 BROWN J s a e BLUE V d v n 2 l s 1 4 7 a a V G GREY t s s 1 a YELLOW G n BLACK i a M W S GREY p 1 2 m e 1 GREY T J 1 h g g i n i H m a ) r r e g l l o 6 o r r t J P n o C 1 g U 1 o n r i c C i t t W M e ( M S S 6 3 5 2 0 BLUE M I 1 1 2 4 1 U J BLUE e s r w v l o o a t l s V F i r r m 5 e e r t t 8 e a 5 a 9 4 8 h J J W W T J S e 0 1 R 4 6 6789 5 d 1 m 1 a o l R J F BLUE 1 3 2 1 3 45 2 e s n e BLACK S e BLACK m a l F N N D D W W E E O O R R R R B B W r K N W E K O o C L O E D W T C L A L I D s O E L A L U E H L E e L R s E R B Y n B B R Y B W r e v l o S t a s V i w M r o m l e r F t e a r h e T W t t t a e e l l t W n u I O s f t o n n A i e e 1 P . c . d r F m n 2 e e e N e t 2 r d / i s a I C n u b e S u a q A h N o e S r e r r A C g h e y t t e t e y a i d l l n l h . i i o w t t a ) , C c u r n r e i l o r o o h c i t a / i t t s c r i n d t e e e d o n l c i c d e i t a e e o l v a t ) c r e e n N n l e b e d o s a r e i t n c r t r s h i a o t u o l u d c s l e ( h l m h e t t i a t i e d t e n w d s o c w e c o , n n r i e s l r C a c i e a u l u l n c c d p o a ( a o o c y p l i d c a r 0 r n y l t 7 o s c e e a i c c e h b o h c l o O w T a l N e O T R OI R P SE RI W LL A LE B A L : N OI T UA C G NI CI V RE S NE H W N OI T CE NN O C SI D NA C SR OR R E G NI RI W . SL O RT N OC SU O RE G NA D D N A R EP O RP M I ES UA C N OI TA R EP O R EP O R P Y FI RE V . N OI TA R EP O . G NI CI V RE S R E TF A Y E R G 6 5 S T H Y E R G 3 2 p U s u i s le C t i e h n e r a F t u o kc o L n w o D ! K C AL B BLUE 4 BLUE K C A L B 1 M I U e m a lF l y t a s m o m f o r o e f n o B o d O N c / o E n M O r o t s i m r e h T k n a T FIGURE 34 www.americanwaterheater.com 35 LIGHTING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTINGFLAMMABLE BEFORE LIGHTING: ENTIRE SYSTEM MUST BE FILLED WITH WATER AND AIR PURGED FROM ALL LINES A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do NOT try to light the burner by hand. B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS • Do not try to light any appliance. • Do not touch any electric switch; do not use any phone in your building. • Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. • If you cannot reach your gas supplier, call the fire department. C. Do not use this appliance if any part has been under water. Immediately contact a qualified installer or service agency to replace a flooded water heater. Do not attempt to repair the unit! It must be replaced! OPERATING INSTRUCTIONS 1. STOP! Read the safety information above on this label. 2. Ensure tank is filled with water and the gas line is connected. 3. This appliance is equipped with a device which automatically lights the burner. DO NOT TRY TO LIGHT THE BURNER BY HAND. 4. Wait five (5) minutes to clear out any gas. If you smell gas, STOP! Follow "B" in the safety information above on this label. If you don't smell gas: 5. Turn on all electrical power to the appliance. 6. If the green light above the stand-by button is flashing, press the stand-by button. If the green light is turned off then the water heater will automatically light the burners. 7. Set the display to the desired setting. CAUTION: Hotter water increases the risk of scald injury. Consult the instruction manual before changing temperature. 8. If the appliance will not operate, follow the instructions "TO TURN OFF GAS TO APPLIANCE" and call your technician or gas supplier. DANGER: DANGER: Hotter water increases the risk of scald injury. Consult the instruction manual before changing temperature. TO TURN OFF GAS TO APPLIANCE 1. Set the thermostat to the lowest setting. 2. Set the ON/OFF switch on the control panel to the "OFF" position. 3. Turn off all electrical power to the appliance if service is to be performed. 36 www.americanwaterheater.com HEAT CYCLE DEFINITIONS STATE DESCRIPTION Pre-purge If the heat engine initial call-for-heat is successful (all checks are passed), the combustion fan is energized. The fan is started at a high speed for several seconds and the system verifi es the fan speed. Input signals (from other parts of the water heater) are verifi ed before completion of pre-purge including fan current verifi cation. If one of the checks fails then the unit moves into the post-purge mode followed by the hard lockout mode and the appropriate error is displayed (see Error Code List and Clear-out Procedure). Inter-Purge If the fl ame presence is detected the control delays a pre-determined amount of time keeping the spark igniter energized. If fl ame presence is not detected within 5 seconds from the moment the gas was allowed in the combustion chamber (three ignition trials) then the control will initiate an ignition re-try for two more times. If fl ame presence cannot be verifi ed within the given timing and after the ignitions' re-try (if applicable), the system enters the post-purge mode and the gas fl ow is turned off. Post-Purge The heat engine gas valve is now turned off and the fan speed is changed to high speed for a predetermined time followed by a change of fan speed to a low value for the remaining duration of the post purge mode. The control will also verify that the proper conditions are maintained and there is no fl ame current sensed from the fl ame rod. If during the fi rst stage of the post-purge mode (high speed fan operation) conditions for a new call for heat are met then the system will allow the state change to "Initial call for heat" only after the fi rst stage of the post-purge mode is complete. Standby Mode After successful completion of post-purge, the fan is turned off and the control will wait until the determined conditions for a call for heat are met. In standby mode the unit continually monitors the input and output conditions and if abnormal conditions are detected the unit will enter in a lockout mode. If a call for heat is required and all checks are passed, the control will return to the initial call for heat state. Lockout mode This is a non-operational mode following the detection of an error in the system. In this stage the system displays an error message and continuously monitors input and output parameters. The system can move from this state into the stand-by mode only if the error is cleared (typical values for input and output parameters are recorded). Proven Ignition Once the power is turned on, the self-inspection is getting a normal status, water is turned on and fan's current is normal then the ignition process will start for 5 seconds. If ignition is successful, the heater will go to normal combustion state and the ignition sparking will stop after 3 seconds. If ignition fails, the control will attempt to cycle through the heating stage three times and then attempt to re-ignite the gas. If ignition cannot be achieved, the control will end ignition attempts and prevent any more heating cycles, close the gas valve, turn the blower on, and display the E28 error message to the user. TABLE 2 www.americanwaterheater.com 37 TEMPERATURE REGULATION FIGURE 35 It is recommended that lower water temperatures be used to avoid the risk of scalding. It is further recommended, in all cases, that the water temperatures be set for the lowest temperature which satisfi es your hot water needs. This will also provide the most energy effi cient operation of the water heater. HOT WATER CAN SCALD: Water heaters are intended to produce hot water. Water heated to a temperature which will satisfy space heating, clothes washing, dish washing, and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infi rm, or physically/ mentally handicapped. If anyone using hot water from this heater fi ts into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap, then you must take special precautions. In addition to using the lowest possible temperature setting that satisfi es your hot water needs, a means such as a mixing valve, should be used at the hot water taps used by these people or at the water heater. Mixing valves are available at plumbing supply or hardware stores (see Figure 3). Follow manufacturer's instructions for installation of the valves. Before changing the factory setting on the thermostat, read the "Temperature Regulation" section in this manual. Never allow small children to use a hot water tap, or to draw their own bath water. Never leave a child or handicapped person unattended in a bathtub or shower. The water heater should be located in an area where the general public does not have access. If a suitable area is not available, a cover should be installed over the thermostat to prevent tampering. The water temperature setting was factory set at the lowest temperature; THIS WATER HEATER IS EQUIPPED WITH AN ADJUSTABLE THERMOSTAT TO CONTROL WATER TEMPERATURE. HOT WATER TEMPERATURES REQUIRED FOR AUTOMATIC DISHWASHER AND LAUNDRY USE CAN CAUSE SCALD BURNS RESULTING IN SERIOUS PERSONAL INJURY AND/OR DEATH. THE TEMPERATURE AT WHICH INJURY OCCURS VARIES WITH THE PERSON'S AGE AND THE TIME OF THE EXPOSURE. THE SLOWER RESPONSE TIME OF CHILDREN, AGED OR DISABLED PERSONS INCREASES THE HAZARDS TO THEM. NEVER ALLOW SMALL CHILDREN TO USE A HOT WATER TAP, OR TO DRAW THEIR OWN BATH WATER. NEVER LEAVE A CHILD OR DISABLED PERSON UNATTENDED IN A BATHTUB OR SHOWER. THE WATER HEATER SHOULD BE LOCATED IN AN AREA WHERE THE GENERAL PUBLIC DOES NOT HAVE ACCESS TO SET TEMPERATURES. SETTING THE WATER HEATER TEMPERATURE AT 120°F (49°C) WILL REDUCE THE RISK OF SCALDS. Some states require settings at specifi c lower temperatures. The water temperature is controlled using the Temperature Control on the Display at the front of the unit (see Figure 3). This control utilizes a temperature probe to determine the tank temperature. The primary temperature probe is located at the top of the tank. The temperature may be adjusted from 90°F (32°C) to 158°F (70°C). The thermostat was adjusted to 105°F (43°C) before the heater was shipped from the factory. It is recommended that lower water temperature be used to avoid the risk of scalding. It is further recommended, in all cases, that the water temperature be set for the lowest temperature which satisfi es your hot water needs. This will also provide the most energy effi cient operation of the water heater and minimize scale formation. Valves for reducing the point-of-use temperature by mixing cold and hot water are available (see Figure 2). Also available are inexpensive devices that attach to faucets to limit hot water temperatures. Contact a licensed plumber or the local plumbing authority. The table below shows the approximate time-to-burn relationship for normal adult skin. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 20°F (11°C). If you experience this type of use, you should consider using lower temperature settings to reduce scald hazards. 38 www.americanwaterheater.com Water Temperature Time for 1st Degree Burn (Less Severe Burns) Time for Permanent Burns 2nd & 3rd Degree (Most Severe Burns) 110°F (44°C) (normal shower temp.) 116°F (47°C) (pain threshold) 116°F (47°C) 35 minutes 45 minutes 122°F (50°C) 1 minute 5 minutes 131°F (55°C) 5 seconds 25 seconds 140°F (60°C) 2 seconds 5 seconds 149°F (65°C) 1 second 2 seconds 154°F (68°C) instantaneous 1 second (U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15,1978) TABLE 3 Setting Desired Temperatures 1. Set the key lock to the "Off" position 2. Select the desired mode button (vacation, energy saver or boost) 3. Using the arrow buttons select the desired temperature Key Lock NOTE: This is a tamper resistant feature. The Key Lock is considered "On" or "Off": • Key Lock is turned "On" one minute after the unit has been plugged in. • Key Lock can then be turned "Off" for one minute by simultaneously pressing the "Up" Button and the "Down" Button for three seconds. When the keys are locked, the Temperature Set-point cannot be increased or decreased, and the Operating Mode cannot be changed. The On/Off Button is not affected by the Key Lock feature. All other buttons are "locked" when the Key Lock is "On". A lock or unlock LED icon will display the condition. The Icon will be composed of 3 components, the base, a locked and an unlocked arc. Operating Mode Selection Operation modes are: Boost (peak demand), Energy Saver and Vacation. Initial conditions after starting-up the control is determined by evaluation of the stored set-point. Vacation Mode is selected if the Temperature Set-point value is less than 100°F (38°C). Boost Mode is selected if the Temperature Set-point value is greater than or equal to 140°F (60°C). Energy Saver Mode is selected for all other Temperature set-point values. Three LED's are used to indicate the Operating Mode Selection Vacation Mode: Yellow LED Energy Saver Mode: Green LED Boost Mode: Orange LED The Operating Modes have the following characteristics: Vacation mode: • Fixed temperature setting of 90°F (32°C) Energy Saver mode: • Temperature range from 100°F to 135°F (38°C to 57°C) in increments of 1°F or 1°C Boost mode: • Temperature range from 140°F to 158°F (60°C to 70°C) in increments of 1°F or 1°C Switching between operation modes is done by pressing the "Mode" Button when the Key Lock is "Off". When a mode is active, the corresponding LED is turned on. Pressing the "Mode" button will cycle between the three possible modes of operation. Each time the "Mode" Button is changed by the user, the controller display is to respond with the following actions: 1. The Temperature Set-point changes to the lowest temperature for the respective mode (e.g. 100°F (38°C) for "Energy Saver" and 140°F (60°C) for "Boost" mode) and is communicated to the master device. 2. The LED corresponding to the new mode is turned on. UNIQUE HYBRID FEATURES Temperature Measurement Temperature Probes The water heater has support for three independent temperature probes: 1. Water Inlet Temperature Probe The water inlet temperature probe contains a thermistor and measures the temperature of the water entering the heat engine enclosure. 2. Water Outlet Temperature Probe The water outlet temperature probe contains a thermistor and measures the temperature of the water leaving the heat engine enclosure. This supply of (hot) water is delivered to the top of the storage tank in close proximity to the outlet fi tting. 3. Tank Temperature Probe The tank probe contains a thermistor and measures the temperature of the water in the storage tank at a specifi c location between the top and the bottom of the tank. www.americanwaterheater.com 39 Water Circulation Pump A circulation pump is integrated into the heat engine for the Hybrid application. The pump serves to push water through the heat engine at a rate that supports optimum recovery time and maximum heat output. The control provides 120Vac, 60Hz line power to the pump to enable operation. Water Flow Measurement 1. Water Flow Sensor The Water Flow Sensor uses a sensor for the detection of the water fl ow. When water fl ows, the sensor rotates and a transistor is switched on and off, producing a pulsing signal with a frequency related to fl ow rate. 2. Water Flow Detection Flow detection is an on/off indication of whether there is suffi cient fl ow through the heat exchanger for normal heating. 3. If the water is less than 0.58 gal/min (2.2 l/min) the unit stops and will start again when the fl ow is above 0.78 gal/min (2.7 l/min). Water Flow Restriction Valve A motorized valve is placed in series with the circulation pump and the heat exchanger of the heat engine. This valve serves to limit the amount of fl ow through the heat engine such that a variable rate of fl ow can be achieved from the fi xed-speed pump. Gas Delivery Safety String The release of gas into the combustion chamber is of critical importance to the safe operation of the heater. The control is a combination of hardware and software that measure and ensure the gas is released only when appropriate for combustion. The term "safety string" applies to those devices or components that directly control the power applied to the gas valves as well as the gas valves themselves. The components are: • main gas valve solenoid, • stage 1 and 2 gas valve solenoids, • exhaust vent high temperature switch, • energy cut out (ECO) temperature switch. Exhaust Vent High Temperature Switch The water heater is designed for plastic vent piping typically used in high effi ciency appliances. To ensure the water heater will not release exhaust gasses at temperatures that would cause the vent piping to melt, a bimetallic switch is mounted on the assembly. The switch used is a normally closed switch which will open when the temperature reaches the maximum design temperature for the venting used. This switch should reset to the closed position when the vent pipe temperature cools suffi ciently. • Opening Temperature is approximately 165°F (74°C) +/- 5°F (2.8°C). • Closing Temperature is approximately 135°F (57°C) +/- 5°F (2.8°C). The power for the main gas valve is to be routed through the Exhaust Vent High Temperature Switch causing the main gas valve to be de-energized immediately when the switch opens. The status of the Exhaust Vent High Temperature switch should be continually monitored by the controller. If an open switch is detected, the control should declare a fault and respond according to the fault. The fault is a continuous lockout. Energy Cut Out (ECO) Temperature Switch The heat exchanger of the heat engine is equipped with a surface-mounted bimetallic switch which opens when the water temperature exceeds the safe operating temperature for the water heater. • Opening Temperature is 185°F +/-9°F (85°C +/-5°C) • Closing Temperature is 149°F +/-6°F (65°C +/-3°C) The power from the main gas valve is to be routed through the ECO switch causing the main gas valve to be immediately de-energized when the switch opens. The status of the ECO switch should be continually monitored by the controller. If an open switch is detected, the control should declare a fault and respond according to the fault. This will be a continuous lockout. Blocked (Exhaust Gas) Outlet Detection If the exhaust air passage is obstructed, the control is to enter a fault state and initiate a controlled shut down. This is an overall safety feature of the control system. Igniter The control has an integrated direct spark ignition, which can turn on, by means of a relay. This feature is integrated onto the controller board. By default, the control will allow for three ignition retries after a failed ignition. Flame Sensor An active fl ame is sensed through a fl ame rod located in the burner assembly in the region of the burners fl ame. The fl ame sense input will be monitored by the control and respond to the presence of the fl ame. Combustion Chamber Temperature Protection (Thermal Fuse) If in any conditions when the temperature increases over 287.6°F (142°C) the High Limit Temperature Fuse melts. This function disconnects the power supply controller, and must be replaced. 40 www.americanwaterheater.com Line Voltage Monitor The control monitors the line voltage provided to the system. If the line voltage is too low, the system components may not operate properly. For diagnostic purposes, the display panel should indicate that the cause was power-related. • If line power is below 102Vac, the water heater will enter the fault state and initiate a controlled shut-down. The fault will automatically clear if the voltage is restored to 102Vac or above. • If line power is above 132Vac, the water heater will enter the fault state and initiate a controlled shut-down. The fault will automatically clear if the voltage is restored to 132Vac or below. TEMPERATURE REGULATION Temperature regulation is the process by which the controller determines when the water heater is to heat water as well as when to stop the heating process. This section defi nes how the water heater is to regulate the temperature. Temperature Units of Measure The water heater control will display the temperatures in either °C or °F (as per selected unit of measure). The main temperature unit is °C and all the calculations, within the control system, are done using temperature values in °C. The display has the capability to perform a conversion from °C to °F. The resulting temperatures in °F will be rounded off to the nearest degree. Temperature Set-point The adjustable temperature set-point is used to determine the desired outlet temperature of the water heater. The water outlet of the heat engine feeds the outlet of the storage tank although some mixing does occur with the water at the top of the storage tank. For this reason, the temperature of water delivered is considered equivalent to the heat engine output temperature. This value is to be set within the acceptable range of 90°F (32°C) and 158°F (70°C) when selecting the operating modes. As a safety measure, the control is to ensure that the set point cannot be adjusted outside of this range. If the water fl ow is turned off and then is turned on, the controller remembers and automatically resets to the last temperature. If a power outage occurs or the unit is energized/de energized by the STANDBY symbol for re-booting, the controller resets to the last temperature setting. After clearing a continuous lockout error code the unit will always go back to the factory default temp setting and mode. Storage Tank Set-point The control is required to maintain a storage tank set-point differential temperature. Storage Tank Call For Heat The storage tank call for heat is generated when the tank thermistor temperature drops below the storage tank set point minus the fi xed storage tank differential. At the end of a call for heat the tank thermistor's temperature is equal to or greater than the storage tank set-point. Temperature Control Modes The temperature control functions can operate under one of the pre-defi ned user-selected control modes. The temperature control mode serves to limit the range of the (heat engine) temperature set-point and the storage tank differential. Please reference the Operating Mode Selection for details of how the set-point and differentials are adjusted for the different modes. In brief, three modes are provided: Vacation Mode, Energy Saver Mode, and Boost Mode. The temperature control mode will be maintained after a power loss. Upon restoring power, the temperature set point is set to the last temperature. The default setting is 105°F (41°C) in the Energy Saver Mode. Outlet Temperature Limit Control Your water heater is designed to provide a constant outlet water temperature. The water heater takes into account dynamic conditions of the heat engine such as the inlet water temperature, fl ow rate, gas fl ow adjustment, etc and establishes the optimum performance. The control will end the call for heat if the outlet thermistor temperature exceeds the set-point by a fi xed amount. The call for heat may be restored if the outlet thermistor temperature drops below the set-point by 5.4°F (3°C) or more. Inlet Temperature Limit Control To add protection to the system, an over-temperature comparison is made on the inlet water temperature. The water heater will end the call for heat if the inlet thermistor temperature is above the set-point. The call for heat may be restored if the inlet thermistor temperature drops below the set-point. www.americanwaterheater.com 41 CONSTANT OUTPUT TEMPERATURE CONTROL While the temperature regulation in the previous section describes the features of temperature monitoring and regulation, your water heater goes beyond the on/off control implied there and implements a gas, air and water fl ow modulation scheme to provide a constant water delivery temperature from the heat engine for the duration of the call for heat. Heat Needed during Normal Operation The amount of heat needed is based on the amount of water fl owing through the heater and the amount of temperature rise that needs to be generated to meet your demands. The system will calculate the amount of heat needed. The temperature regulation will prevent the inlet temperature from reaching the temperature set-point. Detection of Failure to Maintain Desired Constant Temperature This check can be used to detect a failure of the stage 2 gas valve. In this case, an insuffi cient amount of heat would be applied. This check can also serve to diagnose failures or mis-wiring of the water fl ow restriction valve. If the valve fails to restrict the fl ow of water, the system may not be able to suffi ciently heat the water passing through the heat engine. A failure to maintain the desired constant temperature is determined by the outlet water temperature remaining 15 degrees lower than the set-point for one minute while the fl ame is established. If this condition is detected while in the heating state for normal modes, an Alert message is provided to the display panel. START UP CONDITIONS Smoke/Odor It is not uncommon to experience a small amount of smoke and odor during the initial start-up. This is due to burning off of oil from metal parts, and will disappear in a short while. NOTE: If there is a discharge from the temperature pressure relief valve, refer to the "THERMAL EXPANSION" section of this manual. NOTE: Do not plug the temperature-pressure relief valve. Strange Sounds Possible noises due to expansion and contraction of some metal parts during periods of heat-up and cool-down do not necessarily represent harmful or dangerous conditions. Condensation causes sizzling and popping within the burner area during heating and cooling periods and should be considered normal. See "CONDENSATE" section. OPERATIONAL CONDITIONS Smelly Water In each water heater there is installed at least one anode rod (see parts section) for corrosion protection of the tank. Certain water conditions will cause a reaction between this rod and the water. The most common complaint associated with the anode rod is one of a "rotten egg smell" in the hot water. The smell is a result of four factors which must all be present for the odor to develop: a. A concentration of sulfate in the supply water. b. Little or no dissolved oxygen in the water. c. A sulfate reducing bacteria which has accumulated within the water heater (this harmless bacteria is nontoxic to humans). d. An excess of active hydrogen in the tank. This is caused by the corrosion protective action of the anode. Smelly water may be eliminated or reduced in some water heater models by replacing the anode(s) with one of less active material, and then chlorinating the water heater tank and all water lines. Contact the local water heater supplier or a qualifi ed service agency for further information concerning an Anode Replacement Kit and this chlorination treatment. If the smelly water persists after the anode replacement and chlorination treatment, we can only suggest that chlorination or aeration of the water supply be considered to eliminate the water problem. Do not remove the anode leaving the tank unprotected. By doing so, all warranty on the water heater tank is voided. "Air" In Hot Water Faucets HYDROGEN GAS: Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable and explosive. To prevent the possibility of injury under these conditions, we recommend the hot water faucet, located farthest away, be opened for several minutes before any electrical appliances which are connected to the hot water system are used (such as a dishwasher or washing machine). If hydrogen gas is present, there will probably be an unusual sound similar to air escaping through the pipe as the hot water faucet is opened. There must be no smoking or open fl ame near the faucet at the time it is open. 42 www.americanwaterheater.com HOUSEKEEPING MAINTENANCE Vacuum around base of water heater for dust, dirt, and lint on a regular basis. VENTING SYSTEM INSPECTION At least once a year a visual inspection should be made of the venting system. You should look for: Obstructions which could cause improper venting. 1. The combustion and ventilation air fl ow must not be obstructed. 2. Damage or deterioration which could cause improper venting or leakage of combustion products. Be sure the vent piping is properly connected to prevent escape of dangerous fl ue gasses which could cause deadly asphyxiation. Obstructions and deteriorated vent systems may present serious health risk or asphyxiation. Chemical vapor corrosion of the fl ue and vent system may occur if air for combustion contains certain chemical vapors. Spray can propellants, cleaning solvents, refrigerator and air conditioner refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, bleach and process chemicals are typical compounds which are potentially corrosive. If after inspection of the vent system you found sooting or deterioration, something is wrong. Call the local gas utility to correct the problem and clean or replace the fl ue and venting before resuming operation of the water heater. BURNER OPERATION AND INSPECTION Flood damage to a water heater may not be readily visible or immediately detectable. However, over a period of time a fl ooded water heater will create dangerous conditions which can cause DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE. Contact a qualifi ed installer or service agency to replace a fl ooded water heater. Do not attempt to repair the unit! It must be replaced! At least once a year a visual inspection should be made of the main burner and spark generator assembly for proper fl ame characteristics and ignition sequences. You should also check for sooting. Soot is not normal and will impair proper combustion. Soot build-up indicates a problem that requires correction before further use. Turn "OFF" gas to water heater and leave off until repairs are made, because failure to correct the cause of the sooting can result in a fi re causing death, serious injury, or property damage. INSTALLED IN SUITABLE AREA: To insure suffi cient ventilation and combustion air supply, proper clearances from the water heater must be maintained. See "Facts to Consider About Location" section. Combustible materials such as clothing, cleaning materials, or fl ammable liquids, etc. must not be placed against or adjacent to the water heater which can cause a fi re. ANODE ROD INSPECTION The anode rod is used to protect the tank from corrosion. Most hot water tanks are equipped with an anode rod. The submerged rod sacrifi ces itself to protect the tank. Instead of corroding the tank, water ions attack and eat away the anode rod. This does not affect the water's taste or color. The rod must be maintained to keep the tank in operating condition. Anode deterioration depends on water conductivity, not necessarily water condition. A water softener can affect the life of the anode installed in this water heater. A corroded or pitted anode rod indicates high water conductivity and should be checked and/or replaced more often than an anode rod that appears to be intact. Replacement of a depleted anode rod can extend the life of your water heater. Inspection should be conducted by a qualifi ed technician, and at a minimum should be checked annually after the warranty period. www.americanwaterheater.com 43 ANODE ROD REPLACEMENT To replace the anode: If the temperature-pressure relief valve on the appliance weeps or discharges periodically, this may be due to 1. Turn off gas supply to the water heater. 2. Shut off the water supply and open a nearby hot-water faucet to depressurize the water tank. 3. Drain approximately 5 gallons (20 litres) of water from tank (Refer to "DRAINING THE TANK" for proper procedures.) Close drain valve. 4. Remove old anode rod. 5. Use Tefl on® tape or approved pipe sealant on threads and install new anode rod. 6. Turn on water supply and open nearby hot-water faucet to purge air from water system. 7. Restart the water heater as directed under "Operating Your Water Heater". See the "Parts Reference Illustration" for anode rod location. thermal expansion. You may have a check valve installed in the water line or a water meter with a check valve. Consult your local water supplier or a qualifi ed service agency for further information. Do not plug the temperature-pressure relief valve. MOTORS Motors are permanently lubricated and do not need periodic lubrication. Keep fan and motor free of dust and dirt by cleaning annually. SNOW ACCUMULATION Keep the area around fl ue terminal free of snow and ice. The appliance will not function properly if the intake air or exhaust is impeded (blocked or partially blocked) by TEMPERATURE-PRESSURE RELIEF VALVE OPERATION FIGURE 36 The temperature-pressure relief valve lever must be operated at least once a year to ensure that the water ways are clear. When checking the temperature-pressure relief valve operation, make sure that: obstructions. CLEANING THE INLET WATER FILTER The cold water inlet fi lter must be cleaned on a regular basis. The frequency of this cleaning is dependent on the quality of your local water supply. You will need to prepare a bucket to collect some of the draining water. The cold water inlet fi lter is located inside the door on the left-hand side of the heat engine. To access the inlet fi lter: Access To Door Pins Door Lock No one is in front of or around the outlet of the 1. temperature-pressure relief valve discharge line. The water discharge will not cause any property 2. damage, as the water may be extremely hot. 3. A discharge line is connected to this valve, directing the flow of hot water from the valve to a proper placement for disposal. If water does not fl ow freely when the lever is in the open position, replacement of the valve is required. Turn off the cold water inlet heater and call a qualifi ed service man. If after manually operating the valve (see Figure 36), it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions, and replace the temperature-pressure relief valve with a new one. FIGURE 37 44 www.americanwaterheater.com Remove the fi lter: • Disconnect the electrical power to the water heater. • Close the shutoff valves on both the hot-water and cold-water lines. • Unlock the door by rotating the side lock counter clockwise with a wide, slot screwdriver. • Pop the top and bottom door pins by pushing the pins out, using a small screwdriver. Open the door. • Open a nearby hot water faucet to depressurize the water tank. • Drain the tank following the instructions in the "Draining The Tank" section. • Unscrew the fi lter and clean by rinsing it under a faucet and scrubbing with a brush if required. Heat Engine Cabinet Water Inlet Filter Water Inlet Fitting FIGURE 38 Install the fi lter: • Install the clean fi lter. • Close the drain valve. • Open the shutoff valves on both the hot-water and cold-water lines. • Fill the tank following the instructions in the "Filling The Water Heater" section in this Manual. • Close and lock the door. • Reconnect the electrical power to the water heater. • Restart the water heater following the Lighting Instructions found in the Operating Manual. CLEANING THE HEAT ENGINE It is imperative that the control compartment burner and circulating air passageways of the appliance is kept clean. • Turn off and disconnect the electrical power. Allow to cool. • Remove and clean the water inlet fi lter. See "Cleaning The Inlet Water Filter" section. • Remove the front panel. • Use a low air pressure to remove dust from the main burner, heat exchanger, and blower. Do not use a wet cloth or spray cleaners on the burners. NOTE: Do not use volatile substances such as benzene and thinners. They may ignite or fade the paint. FLUSHING THE HEAT EXCHANGER (LIME BUILD UP) The heat exchanger must be cleaned on a regular basis to reduce lime build-up. The frequency of this cleaning is dependent on the quality of your local water supply. Failure to fl ush the appliance will cause damage to the heat exchanger. Damage caused by lime build-up is not covered by the unit's warranty. • Disconnect electrical power to the water heater. • Close the shutoff valves on both the hot water and cold water lines. • Drain the tank using the instructions in the "Draining The Tank" section. • Disconnect the hoses joining the tank and the heat engine (upper hose is water outlet and lower hose is water inlet). • Connect addition length of hose (not provided) to existing hoses. (Note: The heat engine hose is a 3/4" NPT thread which is different for a garden hose thread.) 5 gallon pail of virgin, food grade, white vinegar (or virgin, food grade, citric acid). Hot Water Line Heat Engine Cold Water Line FIGURE 39 • Connect a pump to the hose running to the heat engine water inlet (lower fi tting). We recommend a submersible utility pump for the circulating pump. (Note: If a submersible pump is not used, connect a hose from the circulating pump to the cleaning solution.) • Pour approximately 4 gallons (15 litres) of virgin, food grade, white vinegar or citric acid into a 5 gallon or greater pail. • Place the "intake" and "output" hoses into the pail of cleaning solution. If a submersible utility pump is used, place the pump into the pail of cleaning solution. • Plug in the circulating pump. • Connect the electrical power to the water heater and run the heat engine. • Operate the heat engine to circulate the cleaning solution through the system for at least 45 minutes. (Note: Lower the temperature below 104°F (40°C) or to vacation mode.) Warning: Water will become hot very quickly. www.americanwaterheater.com 45 • Disconnect electrical power to the water heater. • Remove the pail of cleaning solution and replace it with a pail of clean water. • Rinse the cleaning solution from the water heater as follows: • Connect the electrical power to the water heater and run the heat engine. • Allow the clean water to fl ow through the heat engine for 5 minutes. • Disconnect electrical power to the water heater and circulating pump. • Disconnect the hoses from the heat engine. • Disconnect hoses and circulating pump, draining the cleaning solution into the pail. • Reconnect the original hoses to the tank. • Remove the in-line fi lter at the cold water inlet and clean out any residue. Assemble the fi lter back into the unit. • Open the shutoff valves on both the hot water and cold water lines. • Fill the tank with water. • Connect the electrical power to the water heater. • Restart water heater following lighting instructions. DRAINING THE TANK The water heater should be drained if being shut down during freezing temperatures. Also periodic draining and cleaning of sediment from the tank may be necessary. FAULT INDICATION AND ERROR CODES A red fault LED (lighting a large red exclamation point) should be present on the display panel if a fault condition exists. A history of the last 9 error codes along with the current error code is stored in memory and can be accessed via the maintenance mode. If the current error code is zero, "E00" shall be displayed (see Table 4). Set the power switch to the "OFF" position. 1. OPEN a nearby hot water faucet and let the water run 2. until it is no longer hot. CLOSE the cold water inlet valve to the water 3. heater. Connect a hose to the drain valve and terminate to 4. an adequate drain. OPEN the water heater drain valve to allow for tank 5. draining. NOTE: If the water heater is going to be shut down and drained for an extended period, the drain valve should be left open with hose connected allowing water to terminate to an adequate drain. CLOSE the drain valve. 6. Follow instructions in the "Filling The Water Heater" 7. section. 8. Follow the lighting instructions on the label or see "Lighting Instructions" in this manual to restart the water heater. 46 www.americanwaterheater.com DIAGNOSTIC DISPLAY By simultaneously pressing the "Mode" and "down arrow" buttons for 3 seconds the unit will allow access to the diagnostic mode. In diagnostic mode, using the up/down arrow allows for cycling between diagnostic codes. The numeric display will show the diagnostic code for 1 second, followed by the actual measurement displayed for 3 seconds. For example, H01 - 105 represents the diagnostic code of "H01" and the value of "105" is the inlet water temperature measurement. The display will continue to show the diagnostic code and the measurement value unless the up or down arrows are pressed to switch to the next item (see Table 4). If no buttons are pressed for 30 seconds the unit will revert back to operation mode where the set-point temperature is displayed. Diagnostic Code Description Code and Measurement Display Format Units (Example of) Displayed characters (Example of) Meaning Remarks H01 Inlet Water Temperature H01 – xxx ºC or ºF 041 or 105 41ºC or 105ºF ºC LED or ºF LED turned ON H02 Heat engine outlet water temperature H02 – xxx ºC or ºF 041 or 105 41ºC or 105ºF ºC LED or ºF LED turned ON H03 Storage tank temperature H03 – xxx ºC or ºF 041 or 105 41ºC or 105ºF ºC LED or ºF LED turned ON H04 Heat engine water fl ow rate H04 – xxx litres/minute 056 5.6 litres/minute (1.48 Gallons/ minute) 1 litre = 0.264 Gallons 1 gallon = 3.78 litres H05 Fan Speed H05 - __x – xxx rpm 006_511 6511 rpm rpm=rotations per minute H06 Fan Current H06 - __x – xxx mA 001_456 1456 mA (1.456A) mA=milliampers H07 Proportional Valve Current H07 – xxx mA 178 178 mA mA=milliampers H08 Total Heating Time H08 – xxx – xxx hours 001_234 1234 hours (51.41 days) H09 Total Cycles H09 – xxx – xxx heating cycles 000_459 459 heating cycles H10 Heat Engine Rated Output H10 – xxx KBtu/hour 100 100 KBtu/hour H11 Current Error Code (See Fault Code Table) H11 – xxx N/A E00 Proper operation - No error H12 – H20 Error Code History, From the Most Recent to the Least Recent (See Fault Code Table) Hxx – xxx N/A E28 Ignition failure The most recent error corresponds to H12 and the least recent to H20 H21 Software Release Number (CWHCB) H21 – xxx – xxx N/A 002_025 Software release number 2.25 For the main controller board H22 Software Release Number (UIM) H22 – xxx – xxx N/A 002_009 Software release number 2.09 For the display board H23 Confi guration File Number H23 – xxx – xxx N/A 000_006 Confi guration fi le number 6 TABLE 4 www.americanwaterheater.com 47 If an error code is displayed, or odd behavior of the unit occurs, the fi rst corrective action should be to "Cycle the Power": Unplug the 120Vac power cord and after 5 seconds plug it in again. If this doesn't clear the fault, proceed with the "Remedy" in the following table (Table 5). If wire harness checking is required, examine the integrity of wires themselves, the connector housings, the integrity of the terminals as well as condition of the crimps. Fault Code Displayed Description Cause Lockout type Remedy E01, E02 Invalid Rated KBtu/Model Type. Control detects that the confi guration selected is not defi ned or the confi guration has never been set. Continuous Change the main controller board (board). E03, E04, E05, E06 Main Valve Relay Out Of Sequence. Control detects that a relay used to enable the Main Valve has failed in either the open or closed position. Soft Change the board. E07 Flame Detected. Flame detected when no fl ame was expected. Soft 1. Check the fl ame rod. 2. Check the fl ame wire harness. 3. Change the board. E08 ECO switch is open. Control detects that the ECO switch is open, preventing power to the Main Valve. Continuous Measure the water temperature. 1. ECO switch open temperature is 85±5ºC (185±14ºF) and close temperature is 65±5ºC (149±14ºF). Check the ECO switch. 2. Check the ECO wire harness. 3. Change the board. 4. E09 High temperature Vent Switch Open. Control detects that the High Temperature Vent Switch is open, preventing power to the Main Valve. Continuous Measure the water temperature. 1. High Vent Switch open temperature is 74±2.8ºC (165±5ºF) and close temperature is 57±2.8ºC (135±5ºF). Check the switch. 2. Check the High Vent Switch wire 3. harness. Change the board. 4. E10 120Vac too high. 120Vac > Overvoltage Limit. Auto Reset Nominal voltage is 120Vac. Overvoltage limit is 132Vac, Undervoltage limit is 102Vac. Check the power cord. 1. Check the wall outlet. 2. Measure the voltage at the board 3. connector J7 between pin1 and pin 3. If the voltage is between limits, change the board. E11 120Vac too low. 120Vac < Undervoltage Limit. E12 Blower Current abnormal. Blower Current meets requirements for a completely blocked fl ue. Soft Check the venting system. If the 1. venting system is clear, recalibrate the unit. 2. Check the blower wire harness. 3. Change the blower. 4. Change the board. E13 Blower Current meets requirements for a partially blocked fl ue. E14 Blower Current meets requirements for a non heating blocked fl ue evaluation. TABLE 5 48 www.americanwaterheater.com Fault Code Displayed Description Cause Lockout type Remedy E15 Blower speed abnormal. Blower speed is 200RPM below the target speed for 20 seconds. Soft 1. Check the blower wire harness. 2. Change the blower. 3. Change the board. E16 Blower speed is 500RPM above the target speed for 6 seconds. E17 Machine starts or normal combustion, but Blower speed = 0 for last 3sec. E18 Have Blower's output signal but the Blower speed = 0 for last 400ms. E19 Blower speed stuck > 3000 rpm Soft E20 Proportional valve (PV) current unusual. Proportional valve Current < Minimum. Soft 1. Check the proportional gas valve wire harness. 2. Change the board. 3. Change the gas valve assembly. E21 Proportional valve Current > Maximum. E22 Outlet Temperature Probe is Open circuit. Outlet Temperature is < minimum defi ned temperature. Soft Check temperature probes wire 1. harness. Replace themperature probe. 2. Change the board. 3. E23 Outlet Temperature Probe is Short circuit. Outlet Temperature is > maximum defi ned temperature. E24 Inlet Temperature Probe is Open circuit. Inlet Temperature is < minimum defi ned temperature. E25 Inlet Temperature Probe is Short circuit. Inlet Temperature is > maximum defi ned temperature. E26 Tank Temperature Probe is Open circuit. Tank Temperature is < minimum defi ned temperature. E27 Tank Temperature Probe is Short circuit. Tank Temperature is > maximum defi ned temperature. E28 Ignition failure. After a failure to detect the fl ame during ignition, the control will retry the specifi ed number of times. After the maximum failed attempts, this fault is declared. Soft 1. Check the igniter wire harness. Check igniter 120Vac voltage 2. supply during the ignition time. Check the ignition rod. If it looks 3. dirty clean it using isopropyl alcohol and a clean cloth. 4. Check the high voltage wiring connection between igniter and igniter rod for proper contact. E29 Outlet water temperature too low. Outlet water temperature <= (setting temperature – 15°C) for 60 seconds after fl ame detected. Alert 1. Check the outlet temperature probe. 2. Change the board. TABLE 5 www.americanwaterheater.com 49 Fault Code Displayed Description Cause Lockout type Remedy E30 Blower Error. Locked Rotor. Soft 1. Check the blower wire harness. 2. Change the blower. 3. Change the board. E33 Water Flow Valve Closed. The water valve did not open when attempting to establish fl ow. Soft 1. Check the water valve wire harness. 2. Change the board. 3. Change the water valve. E34 Proportional Valve (PV) Response Too Slow. The closed loop control of the proportional valve is not functioning properly (control error) or the valve is responding slowly (valve failure). Soft Check the proportional gas valve wire harness, change the board, change the gas valve assembly E35 Repeated Flame Loss Fault. Low Gas Inlet Pressure. Soft Check the fl ame rod wire harness, check line gas pressure. If it is above 5" WC check the fl ame rod and if it looks dirty, clean it up using isopropyl alcohol and a clean cloth, change the fl ame rod, change the board E36 Calibration error. Calibration sequence incomplete because end of "call-for-heat" during the calibration time, or calibration sequence not initiated because of lack of "call-for-heat", or the unit has been never calibrated or Calibration is successful but DIP switch 4 not set to "normal". Soft Unplug the power cord, check the 1. DIP switch 4 position and put it in ON position. Increase the set point so that a 2. "call-for-heat" occurs. Drain the tank in order to lower the 3. water temperature so that a "call for-heat" is generated. 4. Set DIP switch 4 to OFF position. 5. Recalibrate the unit. 6. Change the board. E37 No Water Flow. The heater could not start because the water fl ow was not established. This can be caused by an air bubble or a blockage in the heat engine water passage, a failed fl ow sensor or a failed circulation pump. Soft Check the water inlet on the heat 1. engine. Make a water draw during fi rst 60 2. seconds after putting the unit in ON mode (to evacuate possible air from the heat engine water passage). Check wire harness for pump, water 3. valve and water fl ow sensor. Check the pump 120Vac voltage 4. supply (the pump shall be energized during the heating mode). Clean or change the water fi lter. 5. Change board. 6. Change pump. 7. Change water valve. 8. E99 Board Failure. An internal diagnostic check on the board has failed. Soft Change the board. TABLE 5 Lockout types: Continuous. Needs "Cycle the Power" or service to restart. Soft. Will try to automatically recover and restart after 20 minutes. Auto. Will automatically restart when voltage returns to acceptable parameters. Alert. Will only display an error code in diagnostic mode. 50 www.americanwaterheater.com TROUBLESHOOTING These guidelines should be utilized by a qualifi ed service agent. Problem Possible Cause(s) What to do NOT ENOUGH HOT WATER STANDBY button turned off. Press switch to turn heater on. No power at outlet. Repair service to outlet. Error Code being displayed Refer to "FAULT INDICATION AND ERROR CODES" section and Table 5 or call service agency or dealer. Set point set too low. Adjust Set point higher. Heater undersized. Reduce hot water use. Low gas pressure Contact dealer. Incoming water is usually cold. Allow more time for heater to reheat. Leaking hot water pipes of fi xtures. Have plumber check and repair leaks. CONDENSATION WATER LEAKS Water on the fl oor under heater. Improperly sealed, hot or cold supply connections, relief valve, drain valve or thermostat threads. See CONDENSATE section. Check for leaks. See Figure 40. Leakage from other appliances or water lines. Inspect other appliances near water heater. Condensation of fl ue products. Refer to CONDENSATE section. LEAKING T&P Thermal expansion in closed water system. Install thermal expansion tank (Do not plug T&P valve). Improperly sealed valve. Check relief valve for proper operation (Do not plug T&P valve). HOT WATER ODORS (refer to cathodic protection) High sulfate or mineral content in water supply. Drain and fl ush heater thoroughly then refi ll. Bacteria in water supply. Chlorinate water supply. HOT WATER TOO HOT Thermostat set too high. Refer to TEMPERATURE REGULATION section. WATER HEATER SOUNDS Condensation dripping on burner. Refer to CONDENSATE above. SIZZLING - RUMBLING NOISE Sediment at bottom of heater tank. Clean sediment from tank. Refer to DRAINING. SOOTING Improper combustion. Refer to Air Requirements. BURNER WILL NOT STAY LIT GOES OUT 4-5 SECONDS High ambient room temperature. Contact a qualifi ed service agency to determine cause. Defective Control board. Replace Control board. Damaged Flame Sensor (Error code E35) Replace Flame Sensor VENT GAS ODORS Lack of air supply. Shut off water heater immediately and contact a qualifi ed service agency to determine cause. Improperly installed vent piping. Downdraft Poor Combustion THERE IS NO WATER AT ALL WHEN THE HOT WATER TAP IS OPENED. The unit display is fl ashing an error code. Check if there is any error code fl ashing on the remote controller. TABLE 6 www.americanwaterheater.com 51 Problem Possible Cause(s) What to do WHEN THE TAP IS OPENED, THERE IS NO HOT WATER OR THE HOT WATER TURNS COLD AND STAYS COLD. a. The hot water fi xture is not suffi ciently open to draw the water through the heater. b. The unit display is an error code. c. There is an external recirculation system installed, or there is a check valve on the recirculation return line. d. Improper sized dip tube. e. Water heater disconnected from electrical power. Check if there is any error code on the display. THE WATER IS NOT HOT ENOUGH. The temperature is set too low. a. Check unit's temperature setting. b. Check for cross plumbing between cold and hot water lines. THE WATER IS TOO HOT. The temperature set too high. Check unit's temperature setting. CANNOT OPEN DOOR. Door pins locked in place. a. Ensure the door lock is unlocked b. Ensure the top and bottom door pins are released by using a small screwdriver to pry the pins in the direction of the door opening. TABLE 6 52 www.americanwaterheater.com SERVICE If a condition persists or you are uncertain about the operation of the water heater contact a qualifi ed service agency. LEAKAGE CHECKPOINTS Use this guide to check a "Leaking" water heater. Many suspected "Leakers" are not leaking tanks. Often the source of the water can be found and corrected. If you are not thoroughly familiar with gas codes, your water heater, and safety practices, contact your gas supplier or qualifi ed installer to check the water heater. Read this manual fi rst. Then before checking the water heater make sure the gas supply has been turned "OFF", and never turn the gas "ON" before the tank is completely full of water. Never use this water heater unless it is completely fi lled with water. To prevent damage to the tank, the tank must be fi lled with water. Water must fl ow from the hot water faucet before turning "ON" gas to the water heater. A *Condensation may be seen on pipes in humid weather or pipe connections may be leaking. A C H A G B G F D E FIGURE 40 B. Small amounts of water from temperature-pressure relief valve may be due to thermal expansion or high water pressure in your area. C. *The temperature-pressure relief valve may be leaking at the tank fi tting. D. Water from a drain valve may be due to the valve being slightly opened. E. *The drain valve may be leaking at the tank fi tting. F. Water in the water heater bottom or on the fl oor may be from condensation, loose connections, or the relief valve. DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken. G. *The hose from the tank to the heat engine may be leaking at the tank fi tting. H. *The fi ttings at the circulation pump may be leaking. Leakage from other appliances, water lines, or ground seepage should also be checked. * To check where threaded portions enter the tank, insert cotton swab between jacket opening and fi tting. If cotton is wet, follow "Draining The Tank" section instructions in the "Maintenance" section and then remove fi tting. Put pipe dope or tefl on tape on the threads and replace. Then follow the instructions in "Filling the Water Heater" section. www.americanwaterheater.com 53 PARTS IDENTIFICATION ITEM # DESCRIPTION A Baffl e, Flue B Hot Water Outlet Nipple (w/ Anode, Heat Trap) C T&P Relief Valve D Cold Water Inlet Nipple (w/ Dip Tube, Heat Trap) E Cover, Back-Flue Gas Return F Top Insulation G Flue Gas Return Duct Assy H Shroud, Back-Tank Assembly I Shroud, Right Side-Tank Assembly J Temperature Switch K Condensate Trap L Baffl e, Exhaust M Hose, 12" Braided (Heat Engine Cold In) N Drain Valve O Tank Thermistor (Probe) P Front Door Lock (Hook Cam) Q Shroud, Right Side-Tank Assembly & Door R Display Subassembly S Heat Engine T Cover, Front-Flue Gas Return U Hi-Limit Temperature Switch V Air Inlet Cover (Direct Vent) W Air Inlet Cover Gasket (Direct Vent) X ECO Switch Y Transformer Z (PCB) Circuit Board Assembly (w/ Base) 1 Power Cord Assembly 2 Flame Sensor 3 Spark Generator 4 Gas Valve 5 Blower Motor Assembly 6 Circulation Pump 7 Internal Flow Valve 8 Front Cover Gasket 9 Water Inlet Fitting (Flange) 10 Inlet Water Filter 11 Return Fitting (Flange) 12 Barbed Fitting 13 Heat Exchanger 54 www.americanwaterheater.com A B C D E F G T S H R I Q P 12 O NM L K J U 13 11 10 9 8 V W X Y Z 1 2 3 4 5 6 7 www.americanwaterheater.com 55 REPLACEMENT PARTS DESCRIPTION KIT # Drain valve 9000058015 T&P relief valve 9003741005 Anode/MG/NIP/HT 9004333005 Anode/AL/NIP/HT 9006291005 Circulation pump assembly 9007173005 Inlet/outlet thermistor (Temp sensor) 9007174005 PCB assembly w/ base 9007175005 12" Hose (braided) 9007176005 Tank thermistor 9007177005 NIP/DIP/TBO/HT 9007178005 Hi limit 85 (ECO) 9007179015 Drain/trap assembly-condensate 9007205005 Heat engine assy 9007206005 Gas valve 9007207005 Diptube J 3/4" (return) 9007208005 Transformer 9007209005 Hi limit Fuse 9007210015 Switch-High Temp 9007211015 Inlet water fi lter 9007423015 Water valve assembly 9007424005 Display assembly with label (English) 9007425005 Display assembly with label (Bilingual) 9007426005 PCB fuse 9007427015 Flame sensor with bracket and gasket 9007428015 Ignitor (w/ spark generator, bracket and gasket) 9007429015 Blower motor assembly 9007430005 Transformer fuse 9007431015 Heat Exchanger 9007577005 56 www.americanwaterheater.com NOTES www.americanwaterheater.com 57 NOTES 58 www.americanwaterheater.com NOTES www.americanwaterheater.com 59 Copyright © 2010 American Water Heater Company. All rights reserved.

Không có nhận xét nào:

Đăng nhận xét

Black &amp; Decker Black&amp;Decker Vacuum NV4820CN, homeappliance

Download! NV2410N NV2420N NV3610N NV3620N NV4820N NV4820CN NW3620N NW4820N ACE 2 BDF 3 GHI 4 ENGLISH (Original instructions) Int...